EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
TROUBLESHOOTING
EAGLEHAWK NX Controller Troubleshooting
The following LEDs of the EAGLEHAWK NX controller can be used for troubleshooting purposes:
•
Power LED (green)
•
Status LED (red)
•
L1 and L2 LEDs (yellow)
•
Tx (sending data on RS485-1) and Rx (receiving data on RS485-1) LEDs
Power LED (green) of EAGLEHAWK NX
case
power LED
meaning
ON
Normal operation.
1
Power supply not OK.
2
OFF
Status LED (red) of EAGLEHAWK NX
case
status LED
meaning
!
Normal operation.
1
OFF after
power-up
2
ON con-
– Indicates an active alarm; is controlled by
tinuously after
power-up
L1 LED
case
bus LED
meaning
L1
Normal operation; Daemon starting.
1
ON con-
tinuously after
power-up
Station starting; if L2 is also flashing, then
2
Flashes
the station has started.
constantly
Severe software problems.
3
OFF
Table 28. EAGLEHAWK NX controller power LED
Table 29. EAGLEHAWK NX controller status LED
Niagara Alarm System; is configurable.
Table 30. EAGLEHAWK NX controller bus L1 LED
remedy
No action necessary.
Check power supply voltage.
►
Check wiring.
►
If problem persists, replace hardware.
►
remedy
No action necessary.
Try powering down and then powering up the
►
EAGLEHAWK NX controller.
If problem persists, replace hardware.
►
remedy
No action necessary.
No action necessary.
Contact TAC.
►