Dc Braking [47] - WEG CFW-11 Programming Manual

Hide thumbs Also See for CFW-11:
Table of Contents

Advertisement

P0325 – Ride-Through Proportional Gain
Adjustable
0.0 to 63.9
Range:
P0326 – Ride-Through Integral Gain
Adjustable
0.000 to 9.999
Range:
Properties:
Vector
Access groups
01 PARAMETER GROUPS
via HMI:
Description:
These parameters configure the vector mode Ride-Through PI controller, which is responsible for keeping the DC
link voltage at the level set in P0322.
U
Ride-Through
d
(P0322)
Normally the factory settings for P0325 and P0326 are adequate for the majority of the applications. Do not
change these parameters.

12.8 DC BRAKING [47]

NOTE!
DC break on the start and/or stop will not be active if P0202=4 (Vector with Encoder mode).
NOTE!
The DC Braking at start does not act when the Flying Start function is active (P0320=1 or 2).
The DC BRAKING consists in the application of direct current to the motor, allowing its fast stopping.
Control Mode
V/f scalar
VVW
Sensorless Vector
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
44 FlyStart/RideThru
R.T. Regulator
-
P0325, P0326
U
d
Figure 12.9 - Ride-Through PI controller
Table 12.7 - Parameters related to the DC braking
DC Braking at Starting
P0299 and P0302
P0299 and P0302
P0299 and P0372
Functions Common to All the Control Modes
Refer to the figure 11.1
or 11.2.
DC Braking at Stopping
P0300, P0301 and P0302
P0300, P0301 and P0302
P0300, P0301 and P0372
Factory
22.8
Setting:
Factory
0.128
Setting:
12-19
12