Line Connection Booksize
2.9 Active Interface Modules (internal cooling)
2.9.3.3
Electronics power supply X124
Table 2-20
Terminal block X124
Terminal
+
+
M
M
Max. connectable cross-section: 2.5 mm
Note
The two "+" and "M" terminals are jumpered in the connector. This ensures the supply
voltage is looped through.
2.9.3.4
Line/power connection
Table 2-21
Type of connection
Terminals
Line supply connection (line supply)
Load connection (load)
Active Interface Module
55 kW
80 / 120 kW
1) for ring cable lugs to DIN 46234
Note
The 55 kW Active Interface Module provides the IP20 degree of protection only with
insulated ferrule and a cross-section > 25 mm
78
Function
Electronics power supply
Electronics power supply
Electronics ground
Electronics ground
2
Designations
L1, L2, L3
U2, V2, W2
Terminal type HDFK 50, 25 mm² cross-section, ferrule
Tightening torque min. 6 Nm
Threaded bolt M8, max. cross-section 120 / 2 x 50 mm²,
tightening torque 13 Nm
Technical specifications
Voltage: 24 V DC (20.4 V - 28.8 V)
Current consumption: max. 1.6 A
Max. current via jumper in connector:
20 A at 55 °C
1)
.
2
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
Booksize Power Units