Line Connection Via A Residual-Current Circuit-Breaker - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

2.13.4

Line connection via a residual-current circuit-breaker

In addition to the implemented protective measures against direct and indirect contact,
selectively tripping AC/DC-sensitive residual-current circuit-breakers (Type B) can be used.
Residual-current circuit-breakers alone are not permissible to provide protection against
direct and indirect contact.
Note
Operation behind residual-current circuit-breakers is currently only possible with the 5 kW,
10 kW, 16 kW, 20 kW and 36 kW Line Modules.
Figure 2-51
Booksize Power Units
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
DANGER
Residual-current circuit-breaker (RCCB)
Line Connection Booksize
2.13 Line connection variants
131

Advertisement

Table of Contents
loading

Table of Contents