Ep Terminals X21 - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules Booksize
3.3 Active Line Modules with external air cooling
3.3.3.5

EP terminals X21

Table 3-15
Terminal block X21
Terminal
1
2
3
4
Max. connectable cross-section: 1.5 mm
Type: Screw terminal 1 (see Connection systems)
If an Active Interface Module is connected, the temperature output of the Active Interface
Module must be connected to terminals 1 and 2.
For operation, 24 V DC must be connected to terminal 3 and ground to terminal 4. Upon
removal, pulse suppression is activated. Feedback is deactivated and the bypass relay
drops out. If the Line Module is not disconnected from the line supply when the EP terminal
is deactivated (e.g. a main contactor is not installed), the DC link remains charged.
NOTICE
If a drive line-up is switched off by means of the line disconnecting device, the voltage at
terminals 3 (EP +24 V) and 4 (EP M) must be interrupted beforehand. This can be carried
out using a leading breaking auxiliary contact (≥ 10 ms), for example.
This protects external loads located parallel to the drive on the same switching component.
166
Designation
+ Temp
- Temp
EP +24 V (enable pulses)
EP M (enable pulses)
2
CAUTION
WARNING
Technical specifications
For the temperature sensor connection on the
Active Interface Module
Voltage 24 V DC
Current consumption: 10 mA
Isolated input
Signal propagation times:
L → H: 100 μs
H → L: 1000 μs
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
Booksize Power Units

Advertisement

Table of Contents
loading

Table of Contents