Technical Data - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

NOTICE
The 24 V terminal adapter may only be withdrawn vertically to the front panel (i.e. not at an
angle)!
3.3.7

Technical data

Table 3-21
Technical data for Active Line Modules with external air cooling, part 1
Internal air cooling
Rated power
Infeed:
Rated power (S1)
1
Infeed power (S6-40 %)
1
Peak infeed power
1
Regenerative feedback:
Continuous regenerative power rating
Peak regenerative power rating
Line supply voltages:
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip threshold
Undervoltage trip threshold
Rated input current:
at 380 V
AC
at 480 V
/528 V
AC
AC
at 480 V (S6-40 %)
Peak current (at 400 V
AC
DC link current:
Rated current
at S6-40 %
Peak current
DC link busbar current carrying
capacity
24 V busbar current carrying capacity
Electronics current consumption
Total power loss
(including electronic losses)
Max. ambient temperature without
derating
Max. ambient temperature with
derating
Booksize Power Units
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
6SL3131–
kW
kW (Pn)
kW (Ps6)
kW (Pmax)
kW
kW
V
ACrms
Hz
V
DC
V
DC
V
DC
V
DC
A
AC
A
AC
A
AC
/480 V
)
A
AC
AC
A
DC
A
DC
A
DC
A
DC
A
DC
A
DC
W
2
°C
°C
3.3 Active Line Modules with external air cooling
7TE21–6AAx
7TE23–6AAx
16
36
16
36
21
47
35
70
16
36
35
70
380 V 3 AC -10 % (-15 % < 1 min) to 480 V 3 AC +10 %
47 to 63 Hz
24 (20.4 - 28.8)
510 - 720
820 ± 2 %
360 ± 2 %
26
58
21 / 19
46 / 42
27
60
54 / 45
107 / 89
27
60
35
79
59
117
100
100
20
20
1.1
1.5
286.4
666
40
40
55
55
Line Modules Booksize
7TE25–5AAx
7TE25–5AA3
+ Active
Interface
Module
55
55
55
55
71
71
91
110
55
55
91
110
88
88
70 / 64
70 / 64
92
92
139 / 116
168 / 140
92
92
121
121
152
176
200
200
20
20
1.9
1.9
945.6
945.6
40
40
55
55
179