System Data - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

System Overview

1.7 System data

1.7
System data
Technical data
Unless explicitly specified otherwise, the following technical data are valid for components of
the SINAMICS S120 booksize drive system.
Electrical data
Line connection voltage
Line frequency
Electronics power supply
Short-circuit current rating SCCR in accordance with
UL508C (up to 600 V)
Interference suppression
to EN 61800-3
Overvoltage category
Degree of contamination
*
If a motor holding brake is used, restricted voltage tolerances (-2/+10 %) may have to be taken into account.
Modules
Line Modules in booksize format
Rated supply voltage
Rated pulse frequency
(for Active Line Modules in booksize format only)
Motor Modules in booksize format
DC link connection voltage
Rated pulse frequency
Environmental conditions
The Safety-Integrated safety function:
The components must be protected against conductive pollution (e.g. by installing them in a cabinet with degree of
protection IP54B acc. to EN 60529).
Provided that conductive pollution can be prevented at the installation site, the degree of protection for the cabinet can be
decreased accordingly.
30
380 V to 480 V 3 AC ±10 %
(-15 % < 1 min)
47 Hz to 63 Hz
24 V DC -15/+20 %*, protective extra-low voltage DVC A
(PELV)
1.1 KW – 298 kW: 42 kA
299 kW – 447 kW: 65 kA
448 kW – 671 kW: 84 kA
672 kW – 1193 kW: 170 kA
>1194 kW: 200 kA
Category C3 (standard)
Category C2 (optional)
for system designs conforming to the documentation
III acc. to EN 60664-1
2 to EN 60664-1
480 V 3 AC
For intallation altitudes above 2000 m see the characteristic
for voltage derating
8 kHz
510 V DC up to 720 V
4 kHz
For higher pulse frequencies the corresponding
characteristic for current derating must be taken into
consideration.