Cabinet Design and EMC Booksize
8.2 Selecting devices required to operate SINAMICS
Table 8-2
Requirements regarding line fuses and circuit-breakers for Active Line Modules
16 kW
I
fuse
35 A
rated
I
0.2 s
>180 A
fuse
I
4 s
>130 A
fuse
I
10 s
>100 A
fuse
I
240 s
>60 A
fuse
Table 8-3
Requirements regarding line fuses and circuit-breakers for Smart Line Modules
I
fuse
rated
I
0.2 s
fuse
I
4 s
fuse
I
10 s
fuse
I
240 s
fuse
See catalog D21.1
Table 8-4
Requirements regarding line fuses and circuit-breakers for the Basic Line Modules
I
fuse
rated
I
0.2 s
fuse
I
4 s
fuse
I
10 s
fuse
I
240 s
fuse
430
36 kW
80 A
>360 A
>260 A
>200 A
>135 A
5 kW
16 A
>70 A
>50 A
>42 A
>30 A
20 kW
50 A
>260 A
>190 A
>145 A
>90 A
55 kW
125 A
>450 A
>350 A
>250 A
>200 A
10 kW
35 A
>100 A
>80 A
>65 A
>45 A
40 kW
80 A
>360 A
>260 A
>200 A
>135 A
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
80 kW
160 A
>650 A
>505 A
>360 A
>280 A
16 kW
35 A
>180 A
>130 A
>100 A
>60 A
100 kW
200 A
>800 A
>600 A
>400 A
>310 A
120 KW
250 A
>865 A
>675 A
>480 A
>380 A
36 kW
80 A
>360 A
>260 A
>200 A
>135 A
Booksize Power Units