Assignment Of Autotransformers To Active Line Modules - Siemens SINAMICS S120 Equipment Manual

Booksize power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

2.13.3.4

Assignment of autotransformers to Active Line Modules

Table 2-41
Autotransformers for 480 / 440 V input voltage
Rated power [kVA]
Autotransformer IP00
Input voltage [V]
Output voltage [V]
Vector group
Permiss. ambient temperature
Operation [°C]
Storage / transport [°C]
Humidity classification in accordance
with EN 60721-3-3
Degree of protection to EN 60529
(IEC 60529) IP00
Order No.
Power loss [W]
Autotransformer IP00
Short-circuit voltage uk [%]
Conn. cross-section, max.
primary/secondary sides
Fuse, primary side
Weight [kg], approx. for
Degree of protection IP00
Terminal arrangement
1) FL = flat-type terminal, drill hole Ø 9 mm
2) ISOKL: B, ta = 40
Booksize Power Units
Equipment Manual, (GH2), 07/2007, 6SL3097-2AC00-0BP5
16 kW
36 kW
21
46.5
480 / 440 V 3 AC ± 10 %; 50 Hz - 5 % to 60 Hz + 5 %
400 V 3 AC
Yna0
-25 to +40, for power de-rating up to +55 °C, ISOKL: H, t
-25 to +80
Cl. 3K5, Condensation and icing excluded
Low air temperature 0 °C (+32 °F)
Degree of protection IP00: _ → Order No. A
4AP2796-0EL40-
4AU3696-
2X_0
0ER20-2X_0
2)
160
430
≤ 1.5
16 mm
35 mm
2
2
35 A gL
80 A gL
29
52
1U1 / 1U3 / 1V1 / 1V3 / 1W1 / 1W3 /
2U1 / 2V1 / 2W1 / N
1U1 to 1W1 = 480 V input, 1U3 to 1W3 = 440 V input,
2U1 to 2W1 = 400 V output, N = neutral point
Line Connection Booksize
2.13 Line connection variants
Active Line Module
55 kW
80 kW
70.3
104
= 40
a
4AU3696-
4AU3996-
2NA00-2X_0
0EQ80-2X_0
550
700
70 mm
Flat termination
2
125 A gL
160 A gL
66
95
Flat termination connections
120 kW
155
4BU4395-
0CB50-8B
700
1)
224 A gL
135
1)
115

Advertisement

Table of Contents
loading

Table of Contents