10. When the operation is complete, unplug the programmer
from the gauge and verify gauge operation.
11. To program the next tank, repeat steps 5 to 10. Note that
the programmer plug must be disconnected to select a tank,
the tank buttons will not respond when the programmer is
plugged in.
Copy one 809-DM gauge display to another (can also copy
from an 808P2 or 810PS/810PS2):
1. Turn on the programmer.
2. Make sure the inch mode is correct.
3. Select a memory location with MEM LOC.
4. Select the tank to be copied to or from using the tank buttons
on the front panel.
5. Plug the programmer plug into the gauge display to be copied
from. Press the COPY button to copy the gauge calibration
into memory.
6. When the operation is complete, unplug the programmer plug
from the first gauge and plug it into the gauge display to be
copied to. Press the PROG button to transfer the calibration
to the second gauge.
7. When the operation is complete, unplug the programmer
from the gauge and verify gauge operation.
8. To program the next tank, repeat steps 4 to 7. Note that the
programmer plug must be disconnected to select a tank,
the tank buttons will not respond when the programmer is
plugged in.
Program a 809-DM gauge display from a table of calibration
values:
1. Obtain a table of inches versus volume
2. Turn on the programmer.
3. Make sure the inch mode is correct.
4. Select a memory location with MEM LOC.
5. Press the CLEAR MEM button to erase any
calibration.
6. Starting at the 0 inch value of volume calibration, use the 0
to decimal, E, F, L, U, or BL buttons on the keypad to enter
the calibration. Press the ENTER button to store the value
in memory. When ENTER is pressed, the inches will go to
Page 18