Omron CJ-Series Operation Manual page 90

Built-in i/o. cpu units
Hide thumbs Also See for CJ-Series:
Table of Contents

Advertisement

Auxiliary Area Data Allocation
Name
Address
Pulse Output 1 Out-
A28104
put In-progress Flag
Pulse Output 1 No-
A28105
origin Flag
Pulse Output 1 At-
A28106
origin Flag
Pulse Output 1 Out-
A28107
put Stopped Error
Flag
PWM(891) Output 0
A28300
Output In-progress
Flag
PWM(891) Output 1
A28308
Output In-progress
Flag
Pulse Output 0 Stop
A444
Error Code
Pulse Output 1 Stop
A445
Error Code
Pulse Output 0
A54000
Reset Bit
Description
ON when pulses are being output from pulse
output 1.
0: Stopped
1: Outputting pulses.
ON when the origin has not been determined for
pulse output 1 and goes OFF when the origin
has been determined.
0: Origin established.
1: Origin not established.
ON when the pulse output PV matches the ori-
gin (0).
0: Not stopped at origin.
1: Stopped at origin.
ON when an error occurred while outputting
pulses in the pulse output 1 origin search func-
tion.
The Pulse Output 1 Output Stop Error code will
be written to A445.
0: No error
1: Stop error occurred.
ON when pulses are being output from
PWM(891) output 0.
0: Stopped
1: Outputting pulses.
ON when pulses are being output from
PWM(891) output 1.
0: Stopped
1: Outputting pulses.
When a pulse output stop error occurred with
pulse output 0, the corresponding error code is
written to this word.
When a pulse output stop error occurred with
pulse output 1, the corresponding error code is
written to this word.
The pulse output 0 PV (contained in A276 and
A277) will be cleared when this bit is turned from
OFF to ON.
Section 4-3
Read/Write Times when data is
accessed
Read only
• Cleared when
power is turned
ON.
• Cleared when
operation starts or
stops.
• Refreshed when
pulse output
starts or stops.
Read only
• Turned ON when
power is turned
ON.
• Turned ON when
operation starts.
• Refreshed when
pulse output
starts or stops.
• Refreshed each
cycle during the
overseeing pro-
cesses.
Read only
• Cleared when
power is turned
ON.
• Refreshed each
cycle during the
overseeing pro-
cesses.
Read only
• Cleared when
power is turned
ON.
• Refreshed when
origin search
starts.
• Refreshed when a
pulse output stop
error occurs.
Read only
• Cleared when
power is turned
ON.
• Cleared when
operation starts or
stops.
Read only
• Refreshed when
pulse output
starts or stops.
Read only
• Cleared when
power is turned
ON.
• Refreshed when
Read only
origin search
starts.
• Refreshed when a
pulse output stop
error occurs.
Read/Write • Cleared when
power is turned
ON.
71

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj1m-cpu22Cj1m-cpu23