Wiring Examples
!Caution When the output is being used as a pulse output, connect a load that requires
Connection Example 2
CJ1M CPU Unit
24-V DC
power
supply for
outputs
CW pulse
output
(Pulse
output)
CCW pulse
output
(Direction
output)
Note The terms in parentheses are for pulse + direction outputs.
an output current between 7 and 30 mA. The Unit's internal components may
be damaged if the current exceeds 30 mA.
If the current is below 7 mA, the output waveform's rising edge and falling
edge will be delayed and the output frequency ratings may not be met. If the
load requires less than 7 mA, install a bypass resistor so that the circuit draws
a current greater than 7 mA (10 mA is recommended.)
Use the following equations to determine the bypass resistor requirements.
V
CC
R ≤
− I
I
OUT
2
V
CC
Power W ≥
R
Circuit Example
CJ1M CPU Unit
24-V DC
5-V DC
power
power
supply
supply
+
+
37
31/33
(31/32)
32/34
(33/34)
39, 40
V
: Output voltage (V)
CC
IN
I
: Output current (A)
OUT
× 4 (Tolerance)
I
: Driver input current
W
R: Bypass resistance (Ω)
Power
supply
V
CC
+
I
OUT
Bypass resistor
Section 3-3
Motor driver
(5-V input type)
(+)
(−)
(+)
(−)
(7 to 30 mA)
↓ R
I
IN
Driver
39

Hide quick links: