Common Data For Modules - Danfoss ADAP-KOOL AK-PC 783 Design Manual

Capacity controller with cascade control, refrigeration control systems
Table of Contents

Advertisement

Common data for modules

Supply voltage
Power consumption
Analog inputs
On/off supply voltage inputs
Relay outputs
SPDT
Solid state outputs
Stepper outputs
Ambient temperature
Enclosure
Weight with screw terminals
Approvals
The mentioned data applies to all modules.
If data is specific, this is mentioned together with the module in question.
10
24 V d.c./a.c. +/- 20%
AK-__ (controller)
AK-XM 101, 102, 107, AK-CM 102
AK-XM 204, 205, 208
Pt 1000 ohm /0°C
Pressure transmitter type AKS 32R / AKS
2050
AKS 32 (1-5 V)
Other pressure transmitter:
Ratiometric signal
Min. and Max. pressure must be set
Voltage signal 0-10 V
Contact function (On/Off )
Low voltage
0 / 80 V a.c./d.c.
High voltage
0 / 260 V a.c.
AC-1 (ohmic)
AC-15 (inductive)
U
Can be used for loads that are cut in and
out frequently, e.g. :
Oil valves, fans and AKV valves
Used for valves with stepper input
During transport
During operation
Material
Density
Mounting
Modules in 100- / 200- / controller-series
EU low voltage directive and EMC require-
ments are complied with
UL 873,
Capacity controller RS8GN202 © Danfoss 11-2013
8 VA
2 VA
5 VA
Resolution: 0.1°C
Accuracy: +/- 0.5°C
Resolution:1 mV
Accuracy +/- 10 mV
Max. connection of 5 pressure transmitters on one module
On at R < 20 ohm
Off at R > 2K ohm
(Gold -plated contacts not necessary)
Off: U < 2 V
On: U > 10 V
Off: U < 24 V
On: U > 80 V
4 A
3 A
Min. 24 V
Max. 230 V
Low and high voltage must not be connected to the same
output group
Max. 240 V a.c. , Min. 48 V a.c.
Max. 0,5 A,
Leak < 1 mA
Max. 1 AKV
20-500 step/s
Separate supply to stepper outputs : 24 a.c./d.c. / 13 VA
-40 to 70°C
-20 to 55°C ,
0 to 95% RH (non condensing)
No shock influences / vibrations
PC / ABS
IP10 , VBG 4
For mounting on panel wall or DIN rail
Ca. 200 g / 500 g / 600 g
LVD tested according to EN 60730
EMC tested
Immunity according to EN 61000-6-2
Emission according to EN 61000-6-3
UL file number: E166834 for XM and CM-modules
UL file number: E31024 for PC-modules
AK-PC 783