First Start Of Control - Danfoss ADAP-KOOL AK-PC 783 Design Manual

Capacity controller with cascade control, refrigeration control systems
Table of Contents

Advertisement

First start of control

Check alarms
1. Go to the overview
Press the blue overview button with the compressor and con-
denser at the bottom left of the display.
2. Go to the Alarm list
Press the blue button with the alarm bell at the bottom of the
display.
3. Check active alarms
4. Remove cancelled alarm from the alarm list
Press the red cross to remove cancelled alarms from the alarm
list.
5. Check active alarm again
88
Capacity controller RS8GN202 © Danfoss 11-2013
In our case, we have a series of alarms. We will tidy them up so that we
only have those that are relevant.
In our case an active alarm remains because the control has stopped.
This alarm must be active when control has not started. We are now
ready for the startup of control.
Please note that active plant alarms are automatically cancelled when the
main switch is in pos. OFF.
If active alarms appear when the control is started the reason for these
should be found and remedied.
AK-PC 783

Advertisement

Table of Contents
loading

Table of Contents