Fault Recti cation

Device Type
Symptom
All
Battery missing
RCC
Mains fail
Detector
Head fault
Sounder
No audio output
Radio Hub
Receiver failure
Detector
Head missing
Sounder
Head missing
All
Tamper
I/O Units
Input short/open
circuit
Radio Hub
Aerial tamper
RCC
Aerial tamper
Radio Hub
Radio interference
All
Batteries low
Recti cation Process
Check battery connections and voltages.
Check the RCCs mains supply.
Check that the device is correctly assembled. Failing this, it is
recommended that the detector is replaced.
Check the devices audio monitoring switches are set
correctly. See the devices installation instructions for more
information.
Try resetting the Radio Hub.
Check that the device is correctly assembled. The fault will
clear upon successful relocation.
Check that the device is correctly assembled. The fault will
clear upon successful relocation.
Check that the device is correctly assembled. The fault will
clear upon successful relocation.
Check the 20k end of line resistor is in place and that
connections are secure.
Check for the 47k end of line resistor when measuring
between the centre pin and the outer screen of both aerials
cables and that connections are secure.
Check for the 47k end of line resistor when measuring
between the centre pin and the outer screen of both aerials
cables and that connections are secure.
Has any electrical equipment recently been installed in close
proximity of the Radio Hub. If so it may need to be moved to
an acceptable distance. See Radio Hub Installation
Instructions for details.
Replace all batteries. See the installation instructions for
more details on speci ed batteries.