Cp Iidentifcation With The Telecontrol Basic Protocol - Siemens CP 1243-1 Operating Instructions Manual

Communications processor for connecting the simatic s7-1200 to control center systems
Table of Contents

Advertisement

Configuration
4.9 Security
● SNMP
Here you make the settings for the SNMP agent on the CP.
See section SNMP (Page 70).
● Certificate manager
See section Certificate manager (Page 72).
In the global security settings of STEP 7 among other things you will find the following
parameter groups:
● VPN groups
Here you configure the VPN communication, refer to the section VPN (Page 74).
● User management
Here you configure the users, roles and rights for the TeleService access, refer to the
section Configuration of the TeleService access (Page 80).
4.9.2

CP iIdentifcation with the TeleControl Basic protocol

In the "CP identification" parameter group, you configure the following information for
authenticating the CP with the telecontrol server:
● Project number
The project number is the same for all telecontrol CPs in a STEP 7 project. TCSB
evaluates project numbers from 1 ... 2000.
If you change the project number, this parameter is changed for all CPs in the STEP 7
project.
● Station number
For each S7-1200 station with a telecontrol CP, an individual station number is
configured. TCSB evaluates station numbers from 1 ... 8000.
● Telecontrol password
Password for the authentication of the CP on the telecontrol server
8 ... 29 characters of the ASCII character set 0x20...0x7e
The password can be the same for all CPs of the STEP 7 project. The same password is
configured in TCSB for this station.
● Access ID
The displayed Access ID is formed from the hexadecimal values of project number,
station number and slot. The parameter of the type DWORD is allocated as follows:
– Bits 0 - 7: Slot
– Bits 8 to 20: Station number
– Bits 21 to 31: Project number
64
Operating Instructions, 04/2017, C79000-G8976-C365-03
CP 1243-1