Configuration
4.10 Data points
4.10.12

Partner stations

4.10.12.1

Partner configuration for DNP3 and IEC data points

Enabling the partners for data points - DNP3 / IEC
Enable all configured partners with which the selected data point will exchange data. You
specify the communications partners of the CP in the "Partner stations" parameter group.
● Partner 1 enabled
In the overview table of the data points, as default Partner 1 is set as the partner of a data
point.
In the "Partner stations" tab, in this case Partner 1 is enabled, the option grayed out.
● Partner n enabled
If you enable a different partner or more partners for this data point in the overview table,
these will be enabled in the "Partner stations" tab and all 4 partners can be selected or
deselected.
4.10.12.2

Partner configuration with TeleControl Basic data points.

Enabling the partner for data points - TeleControl Basic
Enable the partner with which the selected data point will exchange data.
A communications can be configured. The telecontrol server and an S7 station cannot be
selected as the partner for a data point at the same time.
The communications partner may be:
● The telecontrol server
Since the telecontrol server is always enabled as a communications partner of the CP, it
is adopted as default in this tab.
The option "Telecontrol server enabled" is selected and grayed out.
● An S7 station
The station must be reachable via the "TeleControl Basic" protocol.
You specify the communications partners of the CP in the "Partner stations" parameter
group.
Activate one of the two options.
● Telecontrol server enabled
Only the telecontrol server is a communications partner of the data point.
● Partner for inter-station communication
Only the S7 station is a communications partner of the data point.