Program Blocks; Program Blocks For Ouc - Siemens CP 1243-1 Operating Instructions Manual

Communications processor for connecting the simatic s7-1200 to control center systems
Table of Contents

Advertisement

Program blocks

5.1

Program blocks for OUC

Using the program blocks for Open User Communication (OUC)
You can use the instructions (program blocks) listed below for direct communication between
S7 stations.
In contrast to other communication types, Open User Communication does not need to be
enabled in the configuration of the CP because corresponding program blocks need to be
created for this. You will find details on the program blocks in the information system of
STEP 7.
Note
Different program block versions
Note that in STEP 7 you cannot use different versions of a program block in a station.
Supported program blocks for OUC
The following instructions in the specified minimum version are available for programming
Open User Communication:
● TSEND_C V3.0 / TRCV_C V3.0
Compact blocks for:
– Connection establishment / termination and sending data
– Connection establishment / termination and reception of data
Use as an alternative:
● TCON V4.0 / TDISCON V2.1
Connection establishment / connection termination
● TUSEND V4.0 / TURCV V4.0
Sending and receiving data via UDP
● TSEND V4.0 / TRCV V4.0
Sending and receiving data via TCP or ISOonTCP
● TMAIL_C V4.0
Sending e-mails
To transfer encrypted e-mails with this block, the precise time of day is required on the
CP. Configure the time-of-day synchronization.
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03
5
117