Datapoint Types - Siemens CP 1243-1 Operating Instructions Manual

Communications processor for connecting the simatic s7-1200 to control center systems
Table of Contents

Advertisement

4.10.3

Datapoint types

Configure the user data to be transferred from the CPU that is referenced via PLC tags of
the CPU on the CP as data points.
The data point types supported by the CP along with the compatible S7 data types are listed
below for the various telecontrol protocols.
The direction relates to the direction of transfer:
● "in": Monitoring direction:
● "out": Control direction
Note
Effect of the change of arrays for data points
If an array is modified later, the data point must be recreated.
Data point types of the "TeleControl Basic" protocol
Table 4- 1
Supported data point types and compatible S7 data types
Format (memory requirements)
Bit
Byte
Integer with sign (16 bits)
Counter (16 bits)
Integer with sign (32 bits)
Counter (32 bits)
Floating-point number with sign (32
bits)
Floating-point number with sign (64
bits)
Data block (1 .. 64 bytes)
For the possible formats of the ARRAY data type, refer to the following section.
1)
Block of data (ARRAY)
With the ARRAY data type, contiguous memory areas up to a size of 64 bytes can be
transferred. The following S7 data types are compatible components of ARRAY:
● Byte, USInt (total of up to 64 per data block)
● Char (total of up to 64 per data block) - CP as of firmware version 2.1.77
CP 1243-1
Operating Instructions, 04/2017, C79000-G8976-C365-03
Data point type
Digital input
Digital output
Digital input
Digital output
Analog input
Analog output
Counter input
Analog input
Analog output
Counter input
Analog input
Analog output
Analog input
Analog output
Data
Data
Direction
S7 data types
in
Bool
in
Bool
in
Byte, Char, USInt
out
Byte, Char, USInt
in
Int
out
Int
in
Word, UInt
in
DInt
out
DInt
in
UDInt, DWord
in
Real
out
Real
out
LReal
out
LReal
in / out
ARRAY
1)
in / out
ARRAY
1)
Configuration
4.10 Data points
Operand area
I, Q, M, DB
Q, M, DB
I, Q, M, DB
Q, M, DB
I, Q, M, DB
Q, M, DB
I, Q, M, DB
Q, M, DB
Q, M, DB
I, Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
Q, M, DB
DB
DB
89