Bosch REXROTH IndraControl VAM 42.1 Project Planning Manual page 57

Machine control panels
Table of Contents

Advertisement

DOK-SUPPL*-VAM*XX.1***-PR02-EN-P
Rexroth IndraControl VAM 12.1/42.1 Machine Control Panels
Wiring 230 V
Fig.7-5:
Limit values of the DC 24 V voltage
min. 16 mm ² ( green/yellow)
Leads
16 mm ² (green/yellow)
Fuses, better: protective motor switches
acc. to EN 60742
N-conductor:
4 mm ² (green/yellow)
Use only with
permission of
the operator!
e.g. drives
Overvoltage category I
(1)
PE bars are to be installed preferably on the mounting plate.
In case of isolated PB bars, both ends must be connected to the mounting plate
by means of copper strips with a maximum length of 20 cm.
The cross-section of the copper strips has to be at least equal to that of the incoming cable.
Fig.7-6:
Wiring 230 V
DANGER
Connect power supply units, which generate protective extra-low voltage
(PELV) (24 V), only to supply voltages for which they are designed. Do
observe the overvoltage categories, see also
55.
Do not apply the supply voltage to the protective extra-low voltage (PELV).
Bosch Rexroth AG
To the housing of the control cabinet
To the machine
6 mm² ( green/yellow)
All housing parts (functional ground)
PE neutral point
16 mm ² (green/yellow)
4 mm ² (green/yellow)
400V
Transformer
230V
(1)
PE
PE
N
U2
4 mm ² (green/yellow)
230 V power supply
operator terminals
service plug receptacle(s)
VAP01.1H-W23
Power unit
VAP01.1H-W23
024-010-NN
DC 24 V
Danger of death by high electric voltage
55/93
Interfaces
Overvoltage category III
Overvoltage category II
Terminals in
isolated
arrangement
Power unit
024-010-NN
DC 24 V
U
L
0 V
U
L
U
Q
U
0 V
Q
"Wiring 230 V " on page