X71: Fieldbus Interface Profibus Dp X71; General Information - Bosch REXROTH IndraControl VAM 42.1 Project Planning Manual

Machine control panels
Table of Contents

Advertisement

DOK-SUPPL*-VAM*XX.1***-PR02-EN-P
Rexroth IndraControl VAM 12.1/42.1 Machine Control Panels
VAM 12.1/VAM 42.1 wiring
7.4

X71: Fieldbus Interface PROFIBUS DP X71

7.4.1

General Information

Fieldbus interface
(4)
U
L
A
(4)
U
0 V
L
A
6 mm ² (blue)
(1)
U
Q
A
(4)
A
6 mm ² (blue)
0 V
U
Q
(1)
FE = Functional earth
B
10 mm ²
(green/yellow)
²n
6 mm
to be connected to FE of VAM .
²a
to be connected to FE of
6 mm
²a
to be connected to FE of the
6 mm
10 mm ² (green/yellow)
(1)
Easily removable and visible
(3)
Polarity reversal of the X1S1 and X10 connectors can destroy the device,
Isolated
A=
if there is not additional external protection (fire danger). This is caused by the
terminal block
simultaneous grounding of the 0 V of the device and of the 0 V (PELV) (1).
B=
Non-isolated
(4)
Cable length between 24 V power supply unit and VAM max. 6 m at a minimum
terminal block
cross-section of 0.75 mm .
Cable length between 24 V power supply unit and VAM max. 10 m at a minimum
cross-section of 1.5 mm .
An additional power supply unit is required if the length exceeds
Fig.7-8:
VAM 12.1/VAM 42.1 wiring
Connector X71 provides at the VP connection 5 V / 100 mA ISO voltage. Do
not use any bus terminating resistors, but only a bus load. Thus, a hand-held
terminal or an Optical Link Plug (OLP) [conversion RS485/Opto] can be con‐
nected.
Optical PROFIBUS networks in ring topology can be established by the OLP.
Type
Electrical isolation
Baud rate
2 BCD rotary switches
Connector X71
Fig.7-9:
Fieldbus interface PROFIBUS DP according to EN 50170, Part 2 (DP)
Bosch Rexroth AG
Overvoltage category I
Terminal block UK6-FSI/6
with automatic cut-out TCP 2 A
(PHOENIX CONTACT)
is recommended.
PLC
VPB 40.3, VPP xx.3, VSB 40.3, VSP xx.3.
UPS (VAU 01.1U).
2
2
RS485
Yes
Up to 12 Mbauds
Station address 1-99
9-pin female connector strip D-SUB
57/93
Interfaces
3
(3)
X10
4
VAM
1
FE
2
Power
supply
unit
1
2
+
(3)
FE
3
X1S1
10 m.