WAGO 750-404 Manual page 43

Wago-i/o-system 750 fieldbus independent counter modules
Table of Contents

Advertisement

An optocoupler is used for electrical isolation between the bus and the field
side.
Any configuration of the counter modules is possible when designing the
fieldbus node. Grouping of module types is not necessary.
The field side supply voltage of 24 V for the counter module is derived from
adjacent I/O modules or from a supply module. The supply voltage for the
field side is made automatically through the individual I/O modules by means
of power jumper contacts.
Warning
The maximum current of the internal power jumper contacts is 10 A. When
configuring the system it is important not to exceed the maximum/sum
current. However, if such a case should occur, another supply module must
be added.
Attention
This module has no power contacts for receiving and transmitting the ground
(earth) potential. A supply module is required, if the adjacent modules need
to be connected to the ground.
Note
Use an appropriate supply module (e.g. 750-602) if an electrically isolated
voltage supply is required!
The module 750-404/000-005 can be used with all couplers/controllers of the
WAGO-I/O-SYSTEM 750 (except for the economy types 750-320, 750-323,
750-324 and 750-327 and the ModBus controllers 750-812, 750-812/025-000
and 750-814).
This description is valid for the XXXX3A05... hardware and software
versions. The version is specified in the manufacturing number, which is part
of the lateral marking on the module.
WAGO-I/O-SYSTEM 750
I/O Modules
750-404/000-005 [2 Up Counter/16 Bit/5 kHz]
• 43
Description

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

I/o-system 750

Table of Contents