YASKAWA SI-EP3 Installation Manual page 44

Profinet ac drive option
Hide thumbs Also See for SI-EP3:
Table of Contents

Advertisement

7 PROFINET Messaging
u
Yaskawa Vendor-Specific Control and Status Words
The Control Word and the Status Word
n
The contents of the Control Word and the Status Word are detailed in
Frequency Reference
n
Frequency Reference is a 16-bit word containing the desired output frequency.
Output Frequency
n
Output Frequency is a 16-bit word containing the current output frequency of the drive.
Table 11 Yaskawa-Specific Control Word and Status Word
Yaskawa-Specific Control Word
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
<1> Bit 11 is not used for GA500.
44
Description
Run bit
Reverse run bit
EF0
Fault Reset
DI1
DI2
DI3
DI4
DI5
DI6
DI7
DI8
<1>
Not Used
Not Used
Not Used
Not Used
YASKAWA ELECTRIC TOBP C730600 89D YASKAWA AC Drive Option SI-EP3 Installation Manual
Table
Yaskawa-Specific Status Word
Bit
Description
0
Running
1
Zero Speed
2
Reverse Operation
3
Reset Signal Input Active
4
At Speed
5
Ready
6
Alarm
7
Fault
8
oPE Fault
9
Uv Return
10
2nd Motor
11
ZSV
12
Not Used
13
Not Used
14
Net Reference
15
Net Control