9 Troubleshooting
Option Fault Monitors U6-98 and U6-99
n
The option can declare error/warning conditions via drive monitor parameters on the drive
keypad as shown in
Fault Condition
No Fault
Force Fault
Network Link Down
Network Failure
Default MAC Address
No IP Address
No Station Name
Bad Station Name
Programmed
Init. Failure
Permanent
Communication Loss
Bad IP Configuration
Two drive monitor parameters, U6-98 and U6-99 assist in network troubleshooting:
• U6-98 displays the first declared fault since the last power cycle. U6-98 is only cleared
upon drive power-up.
• U6-99 displays the present option SI-EP3 status. U6-99 is cleared upon a network-issued
fault reset and upon power-up.
If another fault occurs while the original fault is still active, parameter U6-98 retains the
original fault value and U6-99 stores the new fault status value.
60
Table
14.
Table 14 Option Fault Monitor Descriptions
Fault Declared
N/A
EF0
bUS
bUS
None
None
None
None
None
bUS
None
YASKAWA ELECTRIC TOBP C730600 89D YASKAWA AC Drive Option SI-EP3 Installation Manual
Status Value
(U6-98/U6-99)
0
No faults.
Network sent a message to force this
3
node to the fault state.
1300
No network link to option board.
1301
Connection with PLC Timeout.
Factory default MAC Address
1303
programmed into the option. Return for
reprogramming.
No IP Address has been programmed
1304
into the option.
No Station Name has been programmed
1305
into the option.
Station Name Programmed is invalid
1306
and must be reprogrammed.
1307
Initialize error on power-up.
Fatal error in MAC/PHY hardware,
1308
requires power cycle to recover.
Invalid IP/subnet/gateway address
1309
programmed into F7-01 to F7-12.
Description