6 Related Drive Parameters
No.
U6-80 to U6-83
U6-84 to U6-87
U6-88 to U6-91
U6-92
U6-93
U6-94
U6-95
U6-97
U6-98
U6-99
40
Table 8 Option Monitors
Name
OPT IP ADR 1 to 4
Online Subnet 1 to 4
Online Gateway
Online Speed
Online Duplex
Online Speed
Online Duplex
OPT SPARE 4
First Fault
Current Fault
YASKAWA ELECTRIC TOBP C730600 89D YASKAWA AC Drive Option SI-EP3 Installation Manual
Description
Displays IP Address currently available;
• U6 -80: First octet
• U6 -81: Second octet
• U6 -82: Third octet
• U6 -83: Forth octet
Displays subnet currently available;
• U6 -84: First octet
• U6 -85: Second octet
• U6 -86: Third octet
• U6 -87: Forth octet
Displays gateway currently available;
• U6 -88: First octet
• U6 -89: Second octet
• U6 -90: Third octet
• U6 -91: Forth octet
Displays CN1 Port 1 link speed currently
available.
Displays CN1 Port 1 duplex setting currently
available.
Displays CN1 Port 2 link speed currently
available.
Displays CN1 Port 2 duplex setting currently
available.
Displays option software version.
Displays first option fault. Refer to
Fault Monitors U6-98 and U6-99 on page 60
for details.
Displays current option fault. Refer to
Fault Monitors U6-98 and U6-99 on page 60
for details.
Range
0 to 255
0 to 255
0 to 255
10, 100
0: Half, 1: Full
10, 100
0: Half, 1: Full
-