7 PROFINET Messaging
Table 9 Control Word for PROFIdrive Communication Profile
Bit
Name
ON
0
OFF1
1
OFF2
2
OFF3
OPERATION_
3
ENABLE
RAMP_OUT_
4
ZERO
5
RAMP_HOLD
6
RAMP_IN_ ZERO
7
RESET
8
INCHING_1
9
INCHING_2
10
REMOTE_CMD
11 to 15
-
42
Value
1
Proceed to READY TO OPERATE.
Emergency OFF. Proceed to OFF1 ACTIVE; proceed further to
0
READY TO SWITCH ON unless other interlocks (OFF2, OFF3) are
active.
1
Continue operation (OFF2 inactive).
Emergency OFF. Proceed to OFF2 ACTIVE; proceed further to
0
SWITCH ON INHIBIT.
1
Continue operation (OFF3 inactive).
Emergency stop. Proceed to OFF3 ACTIVE; proceed further to
0
SWITCH-ON INHIBIT.
1
Proceed to ENABLE OPERATION.
0
Inhibit operation. Proceed to OPERATION INHIBIT.
Normal operation. Proceed to RAMP FUNCTION GENERATOR:
1
ENABLE OUTPUT.
0
Stop according to selected stop type.
1
Normal operation.
Proceed to RAMP FUNCTION GENERATOR: ENABLE
0
ACCELERATOR. Halt ramping (Ramp Function Generator output
held).
Normal operation. Proceed to OPERATING. Note: This bit is
1
effective only if the fieldbus interface is set as the source for this
signal by drive parameters.
0
Force Ramp Function Generator input to zero.
0 -> 1
Fault reset if an active fault exists. Proceed to SWITCH ON INHIBIT.
0
(Continue normal operation)
-
Inching 1. (Not supported)
-
Inching 2. (Not supported)
1
Network control enabled.
0
Network control disabled.
-
Reserved
YASKAWA ELECTRIC TOBP C730600 89D YASKAWA AC Drive Option SI-EP3 Installation Manual
Proceed to STATE/Description