Hayward ProLogic Troubleshooting Manual page 36

Residential
Hide thumbs Also See for ProLogic:
Table of Contents

Advertisement

6. Heater Not Firing
The ProLogic features a normally open circuit for each heater. When heat is called for,
based on the temp set point and water sensor, the low voltage contact will close; once
closed, the low voltage supplied by the heater (12-24VAC) should be returned to it.
Check main circulation pump
Verify the heater LED is ON
Step 6A
Step 6B
On the display, verify that the Filter relay is activated
On the local display, with the main circulation pump
(denoted by an illuminated Filter LED). Also, verify the
running, verify the Heater LED is illuminated. IF the
main circulation pump is running. IF the pump is off and
heater LED is not illuminated, go to step 6C. IF the
cannot be turned on through the controller, go to
heater LED is illuminated, proceed to step 6D to test
section 7. IF pump is running, proceed to step 6B.
the heater relay.
36