Supplementary system components
7.4 Controller Extension CX32
Features
Stripped length
Tool
Tightening torque
Max. current carrying capacity, incl. loop-through
Max. cable length
Interface assignments
Table 7-18
Pin
1
2
3
4
Signal type: VI = Voltage input (power supply) VO = Voltage output (power supply)
Note
The 24 V supply voltage is looped through via the 24 V connector. In this case, pin 1 is
jumpered with pin 2, and pin 3 is jumpered with pin 4.
7.4.2.5

Measuring sockets

Application
The T0, T1 and T2 measuring sockets are used to output analog signals. Any interconnectable
signal can be output on any measuring socket of the CX32.
Note
The measuring sockets should be used exclusively for servicing purposes.
The measurements may only be performed by appropriately trained specialists.
The measuring sockets are suited for multiple-spring wire connectors with a diameter of 2 mm.
102
Flexible, with wire-end ferrule without plastic
sleeve
Flexible, with wire-end ferrule with plastic
sleeve
AWG / kcmil
Power supply X124
Signal name
+
+
G
G
Type
0.2 mm² ... 2.5 mm²
0.2 mm² ... 1.5 mm²
22 ... 12
6 ... 7 mm
Screwdriver 0.5 x 3 mm (M2.5)
0.4 to 0.5 Nm
20 A (15 A per UL/CSA)
10 m
Signal type
VI
VI
VO
VO
Meaning
Power supply 24 V
Power supply 24 V
Ground
Ground