Profibus Dp Interfaces - Siemens SIMOTION D4x5 Series Manual

Hide thumbs Also See for SIMOTION D4x5 Series:
Table of Contents

Advertisement

Interfaces

4.6 PROFIBUS DP interfaces

4.6
PROFIBUS DP interfaces
Features of the interface
Table 4-12
Features
Connector type
Cable type
Maximum cable length
Interface assignment for X126
Table 4-13
Pin
1
2
3
4
5
6
7
8
9
The 1P5 voltage is provided exclusively for the bus terminal.
No OLPs are permitted.
Signal type: VO = Voltage output (power supply) O = Output B = Bidirectional
Interface assignment for X136
Table 4-14
Pin
1
2
3
4
5
6
7
8
9
60
Interfaces X126 and X136
PROFIBUS DP interface X126
Signal name
Signal type
--
--
G
VO
1RS_DP
B
1RTS_DP
O
1G
VO
1P5
VO
P24_SERV
VO
1XRS_DP
B
--
--
PROFIBUS DP interface X136
Signal name
Signal type
--
--
G
VO
2RS_DP
B
2RTS_DP
O
1G
VO
1P5
VO
P24_SERV
VO
2XRS_DP
B
--
--
Type
9-pin SUB‑D socket
PROFIBUS cable
100 m at 12 Mbps
Meaning
Reserved, do not use
Ground to P24_SERV
RS-485 differential signal
Request to send
Ground to 1P5
5 V power supply for bus terminal, external, short-circuit proof
24 V for teleservice, short-circuit proof, 150 mA maximum
RS-485 differential signal
Reserved, do not use
Meaning
Reserved, do not use
Ground to P24_SERV
RS-485 differential signal
Request to send
Ground to 1P5
5 V power supply for bus terminal, external, short-circuit proof
24 V for teleservice, short-circuit proof, 150 mA maximum
RS-485 differential signal
Reserved, do not use
SIMOTION D4x5
Manual, 04/2014

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simotion d425Simotion d445Simotion d435Simotion d445-1