Huawei UPS5000-S-1200 kVA User Manual page 125

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Figure 4-30 Battery settings 3
Item
Battery string
sharing
Battery type
Single battery
voltage (V)
Single battery
capacity (Ah)
Batteries in a
battery string
Number of
battery strings
Installation
time
Maintenance
period (d)
Chg. cur.
limiting coef.
Issue 04 (2019-06-25)
Description
Two power units share battery
strings.
Currently, only lead-acid
batteries are supported.
Specifies the voltage of each
battery that is connected in the
battery string in series.
Specifies the capacity of each
battery that is connected in the
battery string in series.
Specifies the number of batteries
in a battery string.
Specifies the number of battery
strings connected in parallel.
A battery maintenance reminder
is displayed when the
maintenance time (counted from
the installation time) comes.
Specifies the interval for
reminding users of battery
maintenance.
If this parameter is set to 0, there
is no reminder.
The charging current limit is a
multiple of the battery capacity.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable, Enable
-
-
12V
2, 6, 12
Depends on the
5–9999
actual model.
2 V battery:
240
6 V battery:
80
12 V battery:
40
1
1–4
-
-
0
0–365
0.1C10
0.05C10 to
0.15C10
2 V battery:
180–300
6 V battery:
60–100
12 V battery:
30–50
117