UPS5000-S-1200 kVA
User Manual
Item
Bus overvolt.
recovery time
Capacitor
failure
detection
Bypass Settings
Item
BPM mode
upon BPM
overtemp.
Lightload BPM
cur. eql. Detect
Issue 04 (2019-06-25)
Description
automatically cleared, and the
rectifier and inverter
automatically start when the bus
voltage recovers (less than 420
V) within Bus overvolt.
recovery time. When Bus
overvoltage recovery is set to
Disable, the bus overvoltage
alarm cannot be automatically
cleared, and the rectifier and
inverter cannot automatically
start.
If Bus overvoltage recovery is
set to Enable, the bus
overvoltage alarm is
automatically cleared, and the
rectifier and inverter
automatically start when the bus
voltage recovers (less than 420
V) within Bus overvolt.
recovery time.
If Capacitor failure detection is
set to Enable, the power module
(power unit) performs inverter
capacitor fault detection based on
the settings of Capacitor failure
detection upper limit and
Capacitor failure detection
lower limit. If the power module
determines that the inverter
capacitor is faulty, it shuts down
the inverter to prevent the fault
from expanding.
Description
Specifies whether to start bypass
mode when overtemperature
occurs.
Enable or disable the light load
bypass current imbalance alarm.
If this parameter is set to Enable,
the load is light (less than 30%
load), and the load rate of a
certain rack is less than 10%, the
system will generate a bypass
current imbalance alarm and
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
5s
5s, 1min, 5min,
10min
Disable
Disable, Enable
Default Value
Value Range
Enable
Disable, Enable
Enable
Disable, Enable
136