Huawei UPS5000-S-1200 kVA User Manual page 204

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0006-1
Mains
undervoltage
0010-1
Abnormal
bypass voltage
0010-2
0011-1
Bypass phase
reversed
0012-1
Bypass neutral
absent
0020-1
Battery
connected
reversely
0021-1
Battery EOD
Issue 04 (2019-06-25)
Severity
Cause
incorrect.
Minor
The mains is
not normal.
The power
module
sampling
circuit is not
normal.
Minor
The bypass
voltage range
is not
correctly set.
The bypass
input voltage
is not normal.
The bypass
frequency
range is not
correctly set.
The bypass
input
frequency is
not normal.
Minor
The phase
sequence of the
three-phase
bypass input is
reversed.
Minor
The neutral wire
of bypass input
is not installed
properly.
Critical
Batteries are not
properly
installed.
Critical
The battery
voltage reaches
the EOD voltage
Copyright © Huawei Technologies Co., Ltd.
Solution
2. Check that the neutral wire to the power
distribution system is normal.
Check whether the mains voltage ranges
from 80 V (excluding 80 V) to 176 V. If no,
the mains monitoring circuit for the power
module is faulty. Replace the faulty
module.
1. Check the bypass input voltage or cable
connections with a multimeter.
2. Check the voltage system and bypass
voltage thresholds configured on the
LCD.
1. Check the bypass input voltage or cable
connections with a multimeter.
2. Check the bypass input frequency.
Check the rated frequency and
frequency range configured on the LCD.
Check whether the cable phase sequence is
correct using a multimeter. If no multimeter
is available, exchange the positions of any
two cables.
1. Secure or connect the neutral wire to the
cabinet if it is loose or disconnected.
2. Check that the neutral wire to the power
distribution system is normal.
1. Check whether battery polarities are
correctly installed by using a
multimeter. If no, correct the
installation.
2. Check whether the battery input voltage
of the UPS is normal. If yes, the battery
sampling circuit of the power module is
faulty. Replace the power module.
If the BCB box is configured, check
whether the BCB box trips. If it trips, close
the BCB box switch.
10 Alarm List
196