Huawei UPS5000-S-1200 kVA User Manual page 120

Hide thumbs Also See for UPS5000-S-1200 kVA:
Table of Contents

Advertisement

UPS5000-S-1200 kVA
User Manual
Item
Maintenance
bypass cabinet
Intelligent
detection
module
Input Settings
Figure 4-25 Input settings
Item
D.G. mode
D.G. power
limiting (kVA)
Issue 04 (2019-06-25)
Description
overdischarge. Intra-rack power
module start delay (s) can be set
to a value ranging from 0.5 to
120. Inter-rack power module
start delay (s) can be set to a
value ranging from 2 to 120. The
preset value of Inter-rack power
module start delay (s) is 5.0.
The start delay of a module in a
rack varies depending on the rack
number and module number. #1
module in rack 1 does not have a
start delay.
If the maintenance bypass unit is
configured, set this parameter to
Enable.
N/A
Description
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
Set these two parameters to
control the valid input current
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Disable
Disable, Enable
Disable
Disable, Enable
Default Value
Value Range
Disable
Disable, Enable
800 kVA
0 kVA to 5000
kVA
112