UPS5000-S-1200 kVA
User Manual
Item
D.G. charger
power ratio (%)
Input cur.
limiting
Input cur.
limiting ratio
(%)
Output Settings
Figure 4-26 Output settings
Item
Output voltage
level
Output volt.
adjustment (V)
Issue 04 (2019-06-25)
Description
and limiting input current, which
prevents load impact and
facilitates better cooperation
between the UPS and the D.G.
Specifies whether to enable or
disable input current limiting to
protect generators.
Limits the input current to protect
the D.G.
Description
Specifies the system output
voltage level. This parameter is
configurable only after the
inverter shuts down. After you
change the voltage level, the
upper limit of the bypass voltage
restores to the default value. (If
the voltage level is 380 V or 400
V, the default upper limit is
+15%. If the voltage level is 415
V, the default upper limit is
+10%.)
The output voltage can be
slightly adjusted based on the
onsite power distribution
condition to ensure a minimum
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
0
0%–100%
Disable
Disable, Enable
200%
50%–200%
Default Value
Value Range
400
380, 400, 415
The default
380 V:
value is 220.0,
209.0–231.0
230.0, and 240.0
400 V:
when the
218.5–241.5
113