4.2 - Physical data 30XA 1002-1702 - units with option 254 and 255** (continued)
30XA
Operating weight*
Sound levels
Standard unit with options 254** or 255**
Sound power***
Sound pressure at 10 m ****
High-energy efficiency unit with option 119** and option 254** or 255**
Sound power***
Sound pressure at 10 m ****
Dimensions - standard unit + options 254/255*
Length
Width
Height
Refrigerant*
Circuit A
Circuit B
Circuit C
Circuit D
Compressors
Circuit A
Circuit B
Circuit C
Circuit D
Oil charge
Circuit A
Circuit B
Circuit C
Circuit D
Capacity control
Minimum capacity
Condensers
Fans
Quantity
Total air flow
Speed
Evaporator
Water volume
Maximum pressure
*
Weights are guidelines only. For sizes 1402 to 1702 weight of modules 1 and 2. The refrigerant charge is given on the unit nameplate.
** Options: 119 = high energy efficiency, 254 = units with copper/aluminium coils, 255 = units with copper/aluminium coils without slots.
*** In dB ref=10-12 W, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
Measured in accordance with ISO 9614-1 and certified by Eurovent.
**** In dB ref 20µPa, (A) weighting. Declared dualnumber noise emission values in accordance with ISO 4871 (with an associated uncertainty of +/-3dB(A)).
For information, calculated from the sound power level Lw(A).
Max. water-side operating pressure without hydronic module.
Notes:
1. Unit sizes 30XA 1402 to 1702 are supplied in two field-assembled modules.
2. Option 119 (high energy efficiency) can be used together with options 254 and 255. Contact your Carrier representative to obtain the performances.

4.3 - Short-circuit stability current for all units

30XA
Short-circuit stability current (TN system)*
Circuits A + B**
kA
Circuits C + D**
kA
Units with option 81
A
30XA
Short-circuit stability current (TN system)*
Circuits A + B**
kA
Circuits C + D**
kA
Units with option 81
A
*
Type of system earthing
**
rms value
20
1002
kg
8870
dB(A)
101
dB(A)
68
dB(A)
103
dB(A)
70
mm
9574
mm
2253
mm
2297
kg
140
teqCO
200.2
2
kg
129
teqCO
184.5
2
kg
-
teqCO
-
2
kg
-
teqCO
-
2
06T semi-hermetic screw compressors, 50 r/s
1
1
-
-
l
27.6
l
27.6
l
-
l
-
Touch Pilot, electronic expansion valve (EXV)
%
15
Copper/aluminium coil
Axial Flying Bird IV fans with rotating shroud
16
l/s
54667
tr/s
11.7
Flooded multi-pipe type
l
140
kPa
1000
252
302
352
402
38
38
38
38
-
-
-
-
-
-
-
-
902
1002
1112
50
50
50
-
-
50
-
-
50
1112
1212
1312
8920
9330
10050
103
102
104
70
69
71
104
103
105
71
70
72
11962
11962
11962
2253
2253
2253
2297
2297
2297
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1
1
1
1
1
1
-
-
-
-
-
-
27.6
36
36
36
36
36
-
-
-
-
-
-
-
-
-
19
20
20
64917
68333
68333
11.7
11.7
11.7
164
174
180
1000
1000
1000
452
504
502
602
38
38
38
50
-
-
-
-
-
-
-
-
1212
1312
50
50
50
50
50
50
1382
1402
1502
10140
4460/8830
4460/8950
104
103
104
71
69
70
105
105
105
72
72
72
11962
9574/4798
9574/4798
2253
2253
2253
2297
2297
2297
-
140
140
-
200.2
200.2
-
103
129
-
147.3
184.5
-
135
135
-
193.1
193.1
-
-
-
-
-
-
1
1
1
1
1
1
-
1
1
-
-
-
36
27.6
27.6
36
27.6
27.6
-
27.6
27.6
-
-
-
-
10
10
20
24
24
68333
82000
82000
11.7
11.7
11.7
189
230
240
1000
1000
1000
702
752
802
854
50
50
50
50
-
-
-
-
-
-
-
-
1382
1402
1502
50
50
50
50
50
50
50
50
50
1702
7880/7880
103
69
105
71
8380/8380
2253
2297
130
185.9
95
135.9
130
185.9
95
66.4
1
1
1
1
27.6
23.5
27.6
23.5
8
28
95667
11.7
240
1000
852
904
50
50
-
-
-
-
1702
50
50
-