3.12 - Multiple chiller installation

It is recommended to install multiple chillers in a single
row, arranged as shown in the example below, to avoid
recycling of warm air from one unit to another.
1.5 m
1.5 m
mini
min.
If the situation at the site does not permit this arrangement,
contact your Carrier distributor to evaluate the various
possible arrangements. In certain situations an accessory
(supplied loose at the time of purchase) can be added.
16
1.5 m
1,5 m
min.
mini

3.13 - Distance to the wall

To ensure correct operation for most cases:
If h < H (2.3 m), minimum S = 3 m
If h > H or S < 3 m, contact your Carrier distributor to
evaluate the various possible arrangements. In certain
situations an accessory (supplied loose at the time of
purchase) can be added.
H
Anti-vibration
mounts
S
h