7 Commissioning
7.3

Final instructions

Fig.63
Example filled-in sticker
Adjusted for / Réglée pour /
Ingesteld op / Eingestellt auf
/ Regolato per / Ajustado
para / Ρυθμισμένο για /
Nastawiony na / настроен
для / Reglat pentru /
настроен за / ayarlanmıştır /
Nastavljen za / beállítva/
Nastaveno pro / Asetettu
kaasulle / Justert for/
indstillet til/ ‫: ل طبض‬
G20
Gas
20
mbar
C
(10)3(X)
C
(12)3(X)
56
AMC Pro
Parameters / Paramètres /
Parameter / Parametri /
Parámetros / Παράμετροι /
Parametry / Параметры /
Parametrii / Параметри /
Parametreler / Paraméterek
/ Parametrit / Parametere /
Parametre / ‫: تاملعملا‬
DP003 - 3300
GP007 - 3300
GP008 - 2150
GP009 -
AD-3001124-01
Values at part load for G31 (propane)
AMC Pro 90
AMC Pro 115
(1) Nominal value
Tab.49
Checking/setting values for O
(butane/propane)
Values at part load for G30/G31 (butane/propane)
AMC Pro 45
AMC Pro 65
AMC Pro 90
AMC Pro 115
(1) Nominal value
Caution
The O
values at part load must be higher than the O
2
full load.
1. Remove the measuring equipment.
2. Screw the cap on to the flue gas measuring point.
3. Seal the gas valve unit.
4. Put the front casing back.
5. Heat the central heating system up to approximately 70°C.
6. Switch the boiler off.
7. Vent the central heating system after approx. 10 minutes.
8. Turn on the boiler.
9. Check the water pressure. If necessary, top up the central heating
system.
10. Fill in the following data on the sticker included, and attach it next to
the data plate on the appliance.
The gas supply pressure;
If set to overpressure application, fill in the type;
The parameters modified for the changes mentioned above.
11. Optimise the settings as required for the system and user
preferences.
See
For more information; Settings, page 57 and User instructions,
page 68.
12. Instruct the user in the operation of the system, boiler and controller.
13. Inform the user of the maintenance to be performed.
14. Hand over all manuals to the user.
O
(%)
(1)
2
5,5
- 5,8
(1)
5,8
- 6,3
(1)
at part load for G30/G31
2
O
(%)
(1)
2
5,7
- 6,2
(1)
5,7
- 6,2
(1)
5,7
- 6,2
(1)
5,7
- 6,2
(1)
values at
2
7725131 - v.01 - 06062019