Appendix B - Alarm Texts - Danfoss AK-PC 781A User Manual

Capacity controller with recovery function
Table of Contents

Advertisement

Appendix B - Alarm texts

Settings
Priority
(factory)
Suction group
Low suction pressure P0
Low
High suction pressure P0
High
High/Low superheat Ss
Medium
Load shedding
Medium
P0/S4/Pctrl sensor error
High
Misc. sensor error
Medium
All compressors
Common safety
High
Comp. 1 safety
Comp. 2 safety
Comp. 3 safety
Medium
_________________
Comp. 10 safety
VSD safety
Medium
Comp. Low oil lvl
Medium
Comp. High oil lvl
Medium
Separator alarms
Medium
Receiver alarm
Medium
Rec. high pressure
Medium
Rec. low pressure
Medium
134
English alarm texts
Low pressure P0
High pressure P0
High superheat suction A
Low superheat section A
Load Shed active
P0A sensor error
S4A sensor error
Pctrl sensor error
Sgc sensor error
Prec sensor error
Pgc sensor error
SsA sensor error
SdA sensor error
Sc3 sensor error
Heat recovery sensor error
Stw sensor error
Shr sensor error
Saux_ sensor error
Paux_ sensor error
Common compr. Safety
cutout
Comp. X oil pressure cut out
Comp. x over current cut out
Comp. 1 motor prot. cut out
Comp. 1 disch. Temp cut out
Comp. 1 disch. Press. Cut out
Comp. 1 General safety cut
out
Comp. 1 FCD safety error
Low oil level comp. x
High oil level in compressor x
Low oil in separator x
No oil separated sep. x
To high oil in separator x
Remaining oil separator x
Oil recv. high level
Oil recv. low level
Recv. High pressure alarm
Recv. Low pressure alarm
Capacity controller RS8HE202 © Danfoss 2017-07
Description
Minimum safety limit for suction pressure P0 has been exceeded
High alarm limit for P0 has been exceeded
Superheat in suction line too high
Superheat in suction line too low
Load shedding has been activated
Pressure transmitter signal from P 0 is defective
Temperature signal from S4 media temp. sensor defective
Pressure transmitter signal from Pctrl is defective
Temperature signal from gas cooler is defective
Pressure transmitter signal from the receiver is defective
Pressure transmitter signal from the gas cooler is defective
Temperature signal from Ss suction gas temp. is defective
Temperature signal from Sd discharge gas temp. is defective
Temperature signal from Sc3 air on condenser defective
Temperature signal from Shrec heat recovery thermostat defective
Temperature signal from hot water circuit is defective
Temperature signal from heat circuit is defective
Signal from extra Temp.sensor Saux_ is defective
Signal from extra pressure sensor Paux_ is defective
All compressors have been cut out on common safety input
Compressor no. x has been cut out on oil pressure safety
Compressor no. x has been cut out on over current safety
Compressor no. x has been cut out on motor protection safety
Compressor no. x has been cut out on discharge temperature safety
Compressor no. x has been cut out on discharge pressure safety
Compressor no. x has been cut out on general safety
Variable speed drive for comp. x has been cut out on safety
Oil level too low in compressor x
Oil level too high in compressor x
Oil level too low in separator x
No oil in oil separator x
Oil level too high in separator x
Separator x can not be emptying total for oil
Oil level too high in receiver
Oil level is too low in receiver
Pressure too high in receiver
Pressure too low in receiver
AK-PC 781A

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents