Page 1
MAKING MODERN LIVING POSSIBLE Manual Superheat Controller, type EKD 316 EKD 316 is a superheat controller for the stepper motor valve that can be used where there are requirements for accurate control of superheat in connection with refrigeration. The controller and valve can be used where there are requirements for accurate control of superheat in connection with refrigeration.
Any external connection with grounding could create a ground Warning loop through a diode in the rectifier bridge which could destroy 21,22 the power supply in EKD 316. Accessories Pressure transducer Temperature sensor External display Programming key...
Data communication Independent superheat regulation Valve driver (Via Analog Signal) Data communication with the EKD 316 is possible using one of the Via standard MODBUS device The superheat in the evaporator is controlled by one pressure This is where the controller receives signals from another following two ways: Communication direct to MODBUS RTU protocol.
Choice of S2 sensor type Surface sensor S2 * Suction pipe of copper or on thin (≤ 3mm) steel pipe. The EKD 316 is normally mounted on a DIN rail, and the necessary Stepper motor output S2 sensor positioning in the suction line Remember to put on heat conducting paste and insulate the connections are shown in the diagram.
Load Defined superheat. The reference follows a defined curve. This curve is defined by Before using the EKD 316 controller, there are settings that have to The parameter SH mode selects the controlling form where it can three values: the closing value, the min. value and the max. value.
1 and then setting parameter o45 to the reducing the value of the Integration Time Tn. The EKD 316 has the traditional PI controlling function with the Kp required opening degree between 0% and 100%. Relay outputs factor for Proportional Gain and Tn for Integration Time in seconds.
Proportional Gain has the following values relative to superheat SH: The force opening of valve function has been implemented in SH min and SH max. the EKD 316 controller. After startup, this function will provide a Evaporator superheat too high 2. Check valve capacity.
Manual Superheat controller type EKD 316 Manual Superheat controller type EKD 316 Appendix I Miscellaneous Controller’s address Menu survey SW = 1.32 If the valve’s opening degree should be controlled with an external signal, the signal is defined as: 0: no signal Fac.
Manual Superheat controller type EKD 316 Manual Superheat controller type EKD 316 Survey of functions Survey and function (continued) Function Para- Parameter by operation via Damping of amplification near reference value Kp Min meter data communication This setting damps the normal amplification Kp, but only just around the reference value.
Reg. type * Example: Depending on the application, control can be carried out based on different param- EKD 316 as simple ETS valve driver function with the following eters. settings: The two possibilities are shown in section "Type of regulation".
Actual value – Values are read/written as 16 bit integer values without decimals. This is the default value as read via modbus Your local Danfoss agent will be pleased to assist with further Scale – This shows the scaling factor of the value. *1 means that there is no scaling. *10 means that the read value is 10 times larger than advice, etc.
Need help?
Do you have a question about the EKD 316 and is the answer not in the manual?
Questions and answers