Configuration - continued
Setup Functions for
General purpose
1. Go to Configuration menu
2. Select General purpose
3. Define number of required
functions
70
In our example we select
one thermostat function for
temperature control in the
compressor room and one alarm
function for monitoring the liquid
level in the receiver.
Capacity controller RS8HE202 © Danfoss 2017-07
The following number of different functions can be
defined:
5 thermostats
5 pressostats
5 voltage signal
10 alarm signals
3 PI-regulations
AK-PC 781A