1. Introduction Application AK-PC 772A is complete regulating units for capacity control of compressors and gas cooler in a small CO 2 refrigeration systems. Either as a compressor and condenser control on MT or as a boost- er system. There can be regulated with one parallel compressor.
Received from the controller via cable. Termination The display must be terminated. Mount a connection between the terminals H and R. (AK-PC 772A is terminated internally.) Placing The display can be placed at a distance of up to 3 m from the controller.
✔ The sum of connections cannot exceed 120 (AK-PC 772A). ✔ The number of extension modules must be limited so that the total power in a row will not exceed 32 VA (including control- ler).
Page 51
MT & LT compressor group and a high pressure control. The example is the same as the one given in the "Design" section, i.e. the controller is an AK-PC 772A + extension modules. Example Compressor Group MT circuit •...
3 compressor of equal size - The capacity curve will look like this Capacity control AK-PC 772A can control up to 3 compressors on MT and 2 on LT. (For parallel compressor operation, however, the system can only control 2 on MT and 2 on LT.) Each compressor can have up to 3 unloaders.
Page 101
The Sgc signal must be stable. If this cannot be done using a sys- tem sensor, it may be necessary to use an immersion tube sensor. If the power supply to AK-PC 772A or the high pressure valve Vhp fails, the system cannot be controlled. We recommend installing an emergency supply (UPS) for both the controller and the valve to avoid faults.
Miscellaneous Supply voltage Sensor calibration: If the power supply to AK-PC 772A or the high pressure valve Vhp The input signal from all connected sensors can be corrected. A fails, the system cannot be controlled. We recommend installing correction will only be necessary if the sensor cable is long and an emergency supply (UPS) for both the controller and the valve has a small cross-sectional area.
Page 112
State a password whether these are correctly attached. c) Select user level d) Select units – either US (e.g. °F and PSI) or Danfoss SI (°C and Note: There is no monitoring when the outlets are overridden. Bar) e) Select language...
Page 115
Stepper Motor Valves Overdrive at Valve Init When selecting a Danfoss stepper motor valve, all settings are fac- During valve initialization, the amount to overdrive the valve, tory set. Here, it is only necessary to select the type of valve.
Page 118
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.