Adaptive defrosting The AK-CC 750A includes an adaptive defrosting function. By using the injection valves opening degree as mass flow sensor for the supply of refrigerant, the controller can monitor ice formation...
Page 5
External display An external display can be fitted in order to show the air tempera- tures around the evaporators. In AK-CC 750A up to 4 displays can be mounted. A graphical display with control buttons can also be fitted. AK-CC 750A...
Page 6
Adaptive defrost AK-CC 750A is equipped with an adaptive defrost function. By using an AKV valve (ETS/CCMT Valve) as mass flow sensor for the supply of refrigerant the control can monitor ice formation on the evaporator.
Received from the controller via cable and RJ11 connector. Termination The display must be terminated. Mount a connection between the terminals H and R. (AK-CC 750A is terminated internally.) Placing The display can be placed at a distance of up to 3 m from the controller.
Data from this example is used in the planning table on the next page. The result is that the following modules should be used: • AK-CC 750A controller • AK-XM 101A • 3 pcs. EKA 163B If the result had demonstrated that an additional output was needed, AK-XM 205A or B would have been the required exten- sion.
• Is connected We have decided to work on the basis of the example we went through previously, i.e. the following modules: • AK-CC 750A controller module • AK-XM 101A analog output module • 3 pcs. EKA 163B display AK-CC 750A...
Page 46
We have decided to describe the setup by means of an example comprising a freezing appliance with 3 evaporators. The example is the same as the one given in the "Design" section, i.e. the controller is an AK-CC 750A + extension modules. Freezing appliance • Refrigerant R134a •...
Introduction Examples Application AK-CC 750A controllers are complete regulating units which The controller has been designed to control one of the following four plant types. together with valves and sensors constitute complete evaporator controls for refrigeration appliances and freezing rooms within Through the programming you determine which one.
If both a stepper valve and a solenoid valve are installed in the controller will not result in liquid throughput to the compressor. Danfoss accepts no responsibility for damage resulting from liquid line, any liquid trapped between the two valves will be inadequate installation.
Page 94
Stepper Motor Valves AKS 32R info When selecting a Danfoss stepper motor valve, all settings are fac- tory set. Here, it is only necessary to select the type of valve. If a valve from other manufacturers is used the following settings has to be made.
Electronic controls are no substitute for normal, good engineering practice. Door contact Danfoss will not be responsible for any goods, or plant compo- Door contact status nents, damaged as a result of the above defects. It is the installer’s...
The refrigerant setting has been changed leak alarm Refrigerant leak A signal is being received from a leak detector Refrigerant (The alarm relay on AK-CC 750A will not be activated) Case cleaning High Case cleaning initiated A case cleaning has been initiated...
Page 106
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.
Need help?
Do you have a question about the AK-CC 750A and is the answer not in the manual?
Questions and answers