1. Introduction SW = 1.4x Application Examples AK-PC 781A is complete regulating units for capacity control of compressors and condensers in refrigeration systems. The con- Traditional capacity control troller is with oil management, heat recovery function and CO 2 gas pressure control.
Received from the controller via cable and RJ11 connector. Termination The display must be terminated. Mount a connection between the terminals H and R. (AK-PC 781A is terminated internally.) Placing The display can be placed at a distance of up to 3 m from the controller.
✔ The sum of connections cannot exceed 120 (AK-PC 781A). ✔ The number of extension modules must be limited so that the total power in a row will not exceed 32 VA (including control- ler).
We have decided to work on the basis of the example we went through previously, i.e. the following modules: • AK-PC 781A controller module • AK-XM 205A input and output module • AK-XM 208C analog input module + stepper output module •...
Page 51
We have decided to describe the setup by means of an example comprising a MT compressor group and a high pressure control. The example is the same as the one given in the "Design" section, i.e. the controller is an AK-PC 781A + extension modules. Compressor Group • MT circuit •...
Pctrl: Control pressure from the low-pressure circuit for cascade Po refrigerant type Select refrigerant type P0 Refrigerant factors K1, K2, K3 Only used if “Po refrigerant type” is set to custom (contact Danfoss for information) Pctrl refrigerant type Select refrigerant type...
(Forced controlled to ON with the setting "Manual" or with the "changeover" on an extension module.) Danfoss recommends this function to avoid any compres- sor damages due to lack of care. (In order to keep things simple, this function is not used as an example.)
4 compressor of equal size - The capacity curve will look like this Capacity control AK-PC 781A can control up to 10 compressors. Each compressor can have up to 3 unloaders. One or two of the compressors can be equipped with speed regulation.
AK-PC 781A allows the injection to begin when the controller is starting. In this way the evaporators will not be filled with liquid ready to run with the first compressor.
The Sgc signal must be stable. If this cannot be done using a sys- tem sensor, it may be necessary to use an immersion tube sensor. If the power supply to AK-PC 781A or the high pressure valve Vhp fails, the system cannot be controlled. We recommend installing an emergency supply (UPS) for both the controller and the valve to avoid faults.
IT compressor is running. The parallel compression (intermediate temperature, ‘IT’) is con- trolled by the third AK-PC 781A. It receives signals from two pres- When the IT capacity’s need drops to min. capacity, the compres- sure transmitters and from the controller on the MT circuit, and it...
Page 125
State a password whether these are correctly attached. c) Select user level d) Select units – either US (e.g. °F and PSI) or Danfoss SI (°C and Note: There is no monitoring when the outlets are overridden. Bar) e) Select language...
Page 127
Stepper Motor Valves Overdrive at Valve Init When selecting a Danfoss stepper motor valve, all settings are fac- During valve initialization, the amount to overdrive the valve, tory set. Here, it is only necessary to select the type of valve.
Page 138
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed.