Configuration - continued
Configuration of inputs
and outputs
1. Go to Configuration menu
2. Select I/O configuration
3. Configuration of Digital outputs
Press the +-button to go on to the
next page
4. Setup On/off inputs
Press the +-button to go on to the
til næste side.
AK-PC 772A
The following displays will depend on the earlier definitions. The dis-
plays will show which connections the earlier settings will require. The
tables are the same as shown earlier.
• Digital outputs
• Digital inputs
• Analog outputs
• Analog inputs
Load
Compressor 1 MT
Compressor 2 MT
Compressor 3 MT
Compressor 1 LT
Compressor 2 LT
Valve and circulation pump hr
Fan
Hot gas dump
We set up the controller's digital outputs by keying in which module
and point on this module each one of these has been connected to.
We furthermore select for each output whether the load is to be active
when the output is in pos. ON or OFF.
Function
Compressor 1 MT Safety
Compressor 2 MT Safety
Compressor 3 MT Safety
All compressors common safety MT
Compressor 1 LT Safety
Compressor 2 LT Safety
All compressors common safety LT
We set up the controller's digital input functions by keying in which
module and point on this module each one of these has been connected
to.
We furthermore select for each output whether the function is to be ac-
tive when the output is in pos. Closed or Open.
Open has been selected here for all the safety circuits. This means that
the controller will receive signal under normal operation and register it
as a fault if the signal is interrupted.
Capacity controller RS8HF102 © Danfoss 2017-07
Output
Module
Point
Active at
DO1
1
12
DO2
1
13
DO3
1
14
DO4
1
15
DO5
1
16
D06
1
17
DO7
1
18
DO8
1
19
Input
Module
Point
Active at
AI1
2
1
AI2
2
2
AI3
2
3
AI4
2
4
AI5
2
5
AI6
2
6
AI7
2
7
3 - Outputs
The possible functions are
the following:
Comp. 1
Unloader 1-1
Unloader 1-2
Unloader 1-3
Do for Compressor. 2 and 3
Compressor run
IT compressor release
Injection suction line
Injection ON
Fan 1 / VSD
Fan 2 - 4
ON
HP Control
ON
Hot gas dump
Heat recovery
ON
Alarm
ON
I'm alive relay
ON
Thermostat 1
ON
Pressostat 1
ON
Volt input 1
PI 1-PWM
ON
4 - Digital inputs
The possible functions are
the following:
Ext. Main switch
Ext. compr. stop
Ext. power loss
Night setback
Load shed 1
Load shed 2
All compressors:
Common safety
Comp. 1
Open
Oil pressure safety
Open
Over current safety
Motor protect. safety
Open
Disch. temp. safety
Open
Disch. press. safety
Open
General safety
Open
VSD comp. 1 Fault
Do for Comp. 2 and 3
Open
Fan 1 safety
Do for fan 2-4
VSD cond safety
AC limit
Rec. low liquid level
Rec. high liquid level
Heat recovery
DI 1 Alarm input
DI 2-10 ...
PI-1 Di ref
External DI PI-1
71