HID-5375 – DIP Switches/Jumpers
SW5
- switches 1 & 2 ON
- switches 3 to 8 OFF
SW2
- switch 1 ON
- switches 2 to 8 OFF
SW1
- switches 1 to 4 ON
- switches 5 to 8 OFF
P4
- jumper ON pins 1 & 2
P3
- jumper ON pins 1 & 2
P2
- jumper ON pins 1 & 2
P1
- jumper on pins 2 & 3
Note - If Pre-alert is
connected, the
reader cannot read
any HID 125 kHz-
compatible card
during the pre-alert
beep.
Black
KI-00204E-07-11
Notes on HID 5375
HID 5375 operates at 12 VDC or 24 VDC. Refer to HID literature for correct jumper settings. If configured
for 12 VDC, do not connect to 24 VDC power supply, otherwise damage to the reader circuit board will
result.
Keyscan Inc. – Technical Guide (PC109x - 07.15)
Figure 54 – HID 5375 Wiring
Shield not
connected.
Isolate with
electrical tape.
6 conductors
shielded 18 AWG
Maximum - 500 ft
(152.4 m)
Shield
Black 1
ACU Ground
Lug
Red
+
VDC
to
separate
DC power
supply
C1
LED D1
(BEEP)
Reader terminal on control board
Yellow (Beeper) used for pre-alert
otherwise isolate and tape back.
If connecting external sound device,
see Pre-Alert Relay Option or refer to
ACU cut sheet enclosed with panel
for ACU/OCB8 relay assignments.
D0
PWR
GND
WHT
GRN
RED
BLK