CIM Diagnostic LEDs B3 – B0
The CIM unit has on-board diagnostic LEDS - B3 to B0 - designed to assist in troubleshooting communication
difficulties.
diagnostic LEDs during boot-up - initial power or Reset J1
data LEDs during operation are TX – transmit
Diagnostic Guidelines
LEDs B3 – B0 indicate TX data transmission states. Diagnostic Jumper J2 - sets the CIM board to run in
diagnostic mode.
CIM Diagnostics – LED Codes
The following table lists diagnostic LED codes on the CIM. LED indicators are as follows:
0 = OFF
1 = ON
Place a jumper on J2 to run the CIM in diagnostic mode.
LED
B3
B2
B1
0
0
0
0
0
0
0
0
1
0
0
1
0
1
0
0
1
0
0
1
1
0
1
1
1
0
0
1
0
0
Note
Diagnostic mode indicated by all four (4) LEDs flashing three (3) times. Diagnostic codes displayed every
20 seconds. Multiple codes displayed lowest to highest.
End of diagnostics routine is indicated when all four (4) LEDs flash three (3) times.
Unless Power Good/Fault LED is flashing, the unit will not enter unit diagnostics mode even if a jumper is
on J2.
Keyscan Inc. – Technical Guide (PC109x - 07.15)
Table 21 – CIM Diagnostic LED Codes
Trouble
Fault
Indication
Code
B0
0
0
None
1
1
+ 5V logic voltage low
0
2
+ 12V input voltage low
1
3
+ 5V isolated logic supply low
0
4
CAN Bus 1 fault
1
5
Global broadcast fail
0
6
ACU panel initialize fail
1
7
CAN Bus 2 fault
0
8
CIM to ACU auto-match bit rate fail or incomplete
1
9
Data carrier detect (DCD) connection lost. Applies to reverse
network communication mode only.