Dps-15 Dual Power Supply - Current Calculation; Table 22 - Keyscan Circuit Board Current Ratings - Keyscan CA250 Series Technical Manual

Hide thumbs Also See for CA250 Series:
Table of Contents

Advertisement

operating maximum of a power supply. See also Keyscan and HID reader voltage/current ratings and Indala
reader voltage/current ratings.
Circuit Board Type
Control Boards
Output Relay Boards
Communication Boards
Specialty Boards
DPS-15 Dual Power Supply – Current Calculation
The DPS-15 power supply has two independent linear 1.2 Amp DC outputs – the ACU supply and the AUX RDR
supply. Use the following two tables for calculating the total current required from the ACU supply and the AUX
RDR supply. Please note the ACU supply and the AUX RDR supply each have an operational limit of 1000 mA.
ACU Supply – 1.2 A
Opposite Add-on Board #, enter the name of the module in the Product Description column and the board's
current requirement in the Current Rating column. Current ratings are in the preceding table and printed on
the circuit boards. Add all the current ratings including the control board to determine the total current.
Keyscan recommends a 200 mA reserve operating margin. The total current from the ACU supply, including
the control board, should not exceed 1000 mA.
Keyscan Inc. – Technical Guide (PC109x - 07.15)
Table 22 – Keyscan Circuit Board Current Ratings
Models
CA250B
CA4500B
CA8500B
EC1500B
EC2500B
OCB-8
CIM
CIM-LINK
NETCOM2
NETCOM2P or NETCOM6P
IOCB1616
WIEEX2 Transmitter (Tx)
WIEEX2 Receiver (Rx)
Current Rating
130 mA
130 mA
130 mA
130 mA
130 mA
230 mA
150 mA
150 mA
270 mA
140 mA
400 mA
50 mA
50 mA
121