Keyscan CA250B Technical Instructions

Ca250 series; ca4500 series; ca8500 series; ec1500 series; ec2500 series;
Hide thumbs Also See for CA250B:
Table of Contents

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Keyscan CA250B

  • Page 2 Information and specifications in this document are subject to change without notice. Except for the benefit of installation and operation of the Keyscan access control system, no part of this documentation may be reproduced or transmitted in any form or by any means without the expressed written permission of Keyscan Inc.
  • Page 4: Table Of Contents

    OCB-8 Relay Board ........................31 Terminate Lock Wiring ........................31 Terminate Input Wiring ........................ 37 Terminate Elevator Floor Wiring ..................... 43 Terminate Reader Wiring at ACU....................47 Terminate Auxiliary Outputs with Hardware/Alarms................49 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 5 Communication Status LEDs ......................87 System Status LED ........................89 Card Diagnostics - LED Wiegand Bit Counters .................. 90 Appendix A – Keyscan & HID Readers ..................... 91 Power Specifications ........................91 Appendix B – Indala Readers ......................112 Power Specifications ........................112 Appendix C –...
  • Page 6 Appendix F – Pre-alert Relay ......................129 Pre-alert ............................ 129 Appendix G – Global Output Relay ....................133 OCB-8/Global IO Assignments ...................... 133 Current Ratings ..........................135 Relay States ..........................136 Warranty ............................138 Index ............................139 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 7: List Of Figures

    Figure 20 – Lock State - Fail Safe Device ....................33 Figure 21 – Lock State - Fail Secure Device ................... 33 Figure 22 – Terminate Lock Wiring CA250B ................... 34 Figure 23 – Terminate Lock Wiring CA4500B ..................35 Figure 24 –...
  • Page 8 Figure 60 – Keyscan K-PROX2 (125 kHz) ....................94 Figure 61 – Keyscan K-VAN Proximity Reader (125 kHz) ................. 95 Figure 62 – Keyscan K-KPR Keypad / Proximity Reader (125 KHz) ............96 Figure 63 – Keyscan K-SMART Reader ....................97 Figure 64 –...
  • Page 9 Figure 85 – WIEEX2 RS485 Connections – (Firmware 6.00 or Higher) ............123 Figure 86 – WIEEX2 to OCB-8 Cable Connection ................... 124 Figure 87 – Accessibility HC Output Relay CA250B/OCB-8 Connections ............ 126 Figure 88 – Accessibility HC Output Relay CA4500B/OCB-8 Connections ..........127 Figure 89 –...
  • Page 10: List Of Tables

    Table 18 – Communication Status LEDs ....................87 Table 19 - System Status LED ......................89 Table 20 – Keyscan & HID Reader Power Specifications ................91 Table 21 – Indala Reader Power Specifications ..................112 Table 22 – Keypad Power Specifications ....................117 Table 23 –...
  • Page 11: Foreword

    Foreword Keyscan systems are designed for use in various environments and applications. As such, ensure correct cable, power, ground, and environment specifications are followed for reliable and safe operation of the equipment. Approved Standards Keyscan CA250, CA4500, CA8500, EC1500 and EC2500 series control units conform to the following approved standards: ...
  • Page 12: Installation Requirements

    We recommend having the following tools on hand to install the access control system:  Digital voltmeter  Wire cutters & needle nose pliers  Soldering iron & tape  Set of screwdrivers  Drill & drill bits  Laptop computer (optional) Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 13: Cables

    Failing to ground the shields or using incorrect cables may cause noise or interference and result in improper card reads. Important Ensure the chassis ground (GND) on the DPS-15 is connected to the metal enclosure ground lug. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 14: Figure 1 - Grounding Access Control Units And Cables With Cims

    ACU 3 KEYSCAN RS232 Tape Earth back shield Tape DPS15 back Control Board shield 40-2322 Data Cable ** RS-232 connections at EGND CIM 0 do not apply when using a NETCOM2P/6P. KI-00470E-07-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 15: Mount The Enclosure & Components

    2 x 16V 40VA transformers or 2 x 16.5V 37VA transformers are connected to the Keyscan DPS-15 power supply  locate the transformers within 30 feet (9.144 m) of the Keyscan DPS-15 power supply - do not mount the transformers inside the ACU metal enclosure ...
  • Page 16: Mounting The Metal Enclosure

    Width - 16" (40.64 cm) ground Depth - 5 1/2" (13.97 cm) lug mount mounts Knockouts Large - 1 3/4" (4.5 cm) Small - 7/8" (2.0 cm) Do not mount enclosure near high-voltage equipment. KI-00104E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 17: Figure 3 - Enclosure Knockout & Mounting Hole Locations/Dimensions

    1.50" (3.81 cm) (3.81 cm) 1.50" (3.81 cm) 0.875" Dia. Knockout Front 8 Places 13.75" (34.925 cm) 11.75" (29.845 cm) 10.25" (26.035 cm) 1.50" (3.81 cm) 1.00" (2.54 cm) KI-00462E-06-12 Bottom View Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 18: Mounting The Pc109X Control Board To Metal Standoffs

    Rev 11, Rev 10 & Rev 9 Control Boards If installing a Rev.11, Rev.10, or Rev. 9 control board in a metal enclosure with the pre-mounted metal standoffs, you require an adaptor kit - P/N – AK2005. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 19: Figure 4 - Mount And Fasten Pc109X Control Board To 3/8" Male/Female Standoffs

    Split Ring enclosure. Lock- Washer washer Front View – Cover removed Ground Lug (diagram not to scale) Stand-off Alternate locations on Ground PC109x control board Mounts PC109x PC109x Alternate Ground Lug Mount KI-00105E-04-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 20: Mounting Power Supplies

    Mounting the DPS-15 Power Supply The Keyscan DPS-15 is a 13.5 VDC dual linear regulated power supply for powering the ACU circuit boards and the readers with the following outputs:  ACU output 12 VDC @ 1.2 Amperes  AUX/RDR output 12 VDC @ 1.2 Amperes...
  • Page 21: Figure 5 - Plastic Stand Off

    Figure 6 – Mounting Power Supplies Hex Nuts x 2 Top of ACU Enclosure Bolts x 2 Top mount location for DPS-15 power supply with CAS6105 plug-in cable to PSC1 terminal. Control Board KI-00107E-06-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 22: Grounding Communication Cable Shield

    When terminating the communication cable in the metal enclosure, ensure that the shield is insulated and connected to the ground lug. Keyscan suggests Alpha PVC 10516 – 16 AWG clear tubing or a comparable tubing to insulate the shield. Do not connect the shield to GND on a communication terminal block.
  • Page 23: Figure 7 - Ca250 With Board Mounting Positions

    OCB-8 CA4500B Locations Optional * NETCOM - use terminal block Control Tamper NETCOM* connections only, not 9-pin male Board Locations Switch connector. (NETCOM refers to NETCOM2 & NETCOM6) PC109x OCB-8 NETCOM KI-00112E-09-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 24: Figure 9 - Ca8500 With Board Mounting Positions

    EC1500B OCB-8 Optional * NETCOM - use terminal block Locations Control Tamper NETCOM* connections only, not 9-pin male Board Switch Locations connector. (NETCOM refers to NETCOM2 & NETCOM6) PC109x OCB-8 NETCOM KI-00114E-09-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 25: Connect Enclosure Tamper Switch To Tb3

    Metal PC109x Enclosure Control Board Connect the yellow wires on the tamper switch to TB3 terminal on the control board. Cut View Protective Cover TAMPER TB3 SWITCH Tamper Switch RS-232 (COM4) KI-00116E-04-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 26: Connect Enclosure Ground Strap

    Optional locations for Front View cover locking screws of Enclosure with Cover Cover Cover Locking Locking Screw Screw 3/8“ x 4 Cover Cover Locking Locking Screw Screw Optional locations for cover locking screws KI-00118E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 27: Typical Door Layout And Hardware

    3/4" conduit to exit to ACU Door contact 1 pair 18 AWG Mag Lock 6 conductors shielded 22 or 18 AWG Reader KEYSCAN Door Strike 36" to 48" (91.4 to 121.9 cm) KI-00119E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 28: Door Lock Hardware

    Permits may be required before installing magnetic locks. Use a battery for temporary power to ensure the door operates properly – alignment, holding, activation, de- activation – before connecting to the Keyscan access control unit. Figure 16 – Typical Door Strike Connection KI-00120E-07-11 Figure 17 –...
  • Page 29: Door Contacts, Exit Buttons, Auxiliary Inputs

    Determines the amount of Lens time the output relays will energize when motion is detected. (RTE - Request To Exit) Auxiliary Input Aux Input NO = Normally Open NC = Normally Closed KI-00122E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 30: Readers

    For mounting readers to a metal surface, consult with the manufacturer's documentation. If a door/reader is located beyond the maximum cable length to the ACU, use a Keyscan WIEEX2 extender kit to a maximum distance of 4000 feet (1219.2 m).
  • Page 31: Terminate Wiring At The Acu

    The following sub-sections review terminating lock, input, elevator, reader, and auxiliary output wiring at the access control units. OCB-8 Relay Board Keyscan’s OCB-8 relay board is used for terminating door locks, magnetic locks, elevator relays, and alarm/auxiliary outputs at the access control unit. Table 3 – OCB-8 Specifications...
  • Page 32 Relay output and DIP switch assignments are noted on the OCB-8 diagrams on the succeeding pages. Keyscan access control units include diodes, Install diodes across all DC door strikes as shown in Figure 23 on page 35. The cathode of the diode connects to the positive side of the strike at the door. The anode of the diode connects to the common return wire.
  • Page 33: Figure 20 - Lock State - Fail Safe Device

    Figure 21 – Lock State - Fail Secure Device 'Normally Open' Relay board positon on relay Door Strike to common on DC power supply supply Lock State Lock Supply Fail Secure Device KI-00125E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 34: Figure 22 - Terminate Lock Wiring Ca250B

    Figure 22 – Terminate Lock Wiring CA250B When OCB-8 connected to CA250B Relay 5 = Aux Output 3 or HC Output 1 Relay 6 = Aux Output 4 or HC Output 2 Do not use relays for both functions. CA250B...
  • Page 35: Figure 23 - Terminate Lock Wiring Ca4500B

    - Fail Safe – to N.C. Ensure all lock ha rdware Diode complies with fed eral, 1N400 4 N.C. state/provincial, and municipal fire cod es. Gro und Lug DC Sup ply KI-00127E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 36: Figure 24 - Terminate Lock Wiring Ca8500B

    Ensure all lock - Fail Secure - hard wa re complie s to N.O. with federa l, state/ Diode provincial, and 1N400 4 12 VDC+ municipal fire cod es. Gro und KI-00128E-10-14 Sup ply Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 37: Terminate Input Wiring

    Examples of exit devices are exit push buttons or motion sensors (PIR) etc. Keyscan recommends a PIR with a pulse output of 1/2 second and suitable for its environment. Security Monitoring Connections A normally-closed device may be connected to an auxiliary alarm input for monitoring stairwell or interior doors, or windows.
  • Page 38: Figure 25 - Terminate Input Wiring - Door Inputs (Contacts)

    AUX Inputs - E Notes Diagram illustrates CA8500B. Connections also apply to CA250B & CA4500B. - CA250B – up to 2 door inputs Door 1 - CA4500B – up to 4 door inputs Non-supervised - CA8500B – up to 8 door inputs Supervision level set in Client software: System VII &...
  • Page 39: Figure 26 - Terminate Input Wiring - Rte Push Button

    Push Button Diagram illustrates CA8500B. Connections also apply to CA250B & CA4500B. - CA250B – up to 2 Request To Exits - CA4500B – up to 4 Request To Exits - CA8500B – up to 8 Request To Exits NO = Normally Open...
  • Page 40: Figure 27 - Terminate Input Wiring - Rte Pir Motion Sensor

    Diagram illustrates CA8500B. Connections also apply to NO = Normally Open CA250B & CA4500B. - CA250B – up to 2 Request to Exits - CA4500B – up to 4 Request to Exits Non-supervised - CA8500B – up to 8 Request to Exits...
  • Page 41: Figure 28 - Terminate Input Wiring Rte - Pir & Push Button

    Notes Diagram illustrates CA8500B. Connections Lens also apply to CA250B & CA4500B. - CA250B – up to 2 Request to Exits PIR (Request To Exit) - CA450B – up to 4 Request to Exits No supervision - CA8500B – up to 8 Request to Exits...
  • Page 42: Figure 29 - Terminate Input Wiring - Ai/Si Inputs

    NC = Normally Closed Connections also apply to CA250B & CA4500B. - CA250B – up to 8 Supervised Auxiliary Alarm Inputs - CA4500B – up to 16 Supervised Auxiliary Alarm Inputs - CA8500B – up to 16 Supervised Auxiliary Inputs...
  • Page 43: Terminate Elevator Floor Wiring

    1 – 8 OCB-8 – H1 Control 2 9 – 16 OCB-8 – H1 Control 3 1 – 8 OCB-8 – H1 Control 4 9 – 16 * Optional OCB-8's must be purchased separately. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 44: Figure 30 - Terminate Floor Wiring Ec1500B

    Fire Panel * OCB-8s must be purchased separately. trips on alarm Ensure all elevator hardware complies with all fire code regulations. N.C. AUX 12 V or ACU 12 V on DPS-15 KI-00134E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 45: Figure 31 - Terminate Floor Wiring Ec2500B

    Fire Panel * OCB-8s must be purchased separately. trips on alarm Ensure all elevator hardware complies with all fire code regulations. N.C. AUX 12 V or ACU 12 V on DPS-15 KI-00135E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 46: Figure 32 - Terminate Floor Input Wiring Ec1500B

    24 of 40 Normally Open Normally Open Normally Open Dry Contact Dry Contact Dry Contact N.O. N.O. N.O. Relay Relay Relay Floor monitoring inputs (separate dry contacts) provided by 3 party elevator company. KI-00136E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 47: Terminate Reader Wiring At Acu

    Green – Data output bit 0  White – Data output bit 1  Blue – Optional pre-alert (reader beeper) For specific reader wiring review the appendices listed in the Table of Contents. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 48: Figure 34 - Terminate Reader Wiring

    AC Fail EGND N.C. DC Output 12V Ground Shield External DC Supply READER PWR FAIL LED D1 (BEEP) FAIL ACU PWR Reader terminal on control board Power terminal on control board KI-00138E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 49: Terminate Auxiliary Outputs With Hardware/Alarms

    Do not assign a time zone to an auxiliary output if the output has previously been assigned to an alarm event. The alarm has priority over the time zone. Figure 35 – Terminate Auxiliary Outputs CA250B When OCB-8 connected to CA250B...
  • Page 50: Figure 36 - Terminate Auxiliary Outputs Ca4500B

    LE D ON = RELA Y cable with J1 E NE RGIZ ED Relay P ower set on ACU. OCB-8 RS-232 (COM4) OCB-8 Relays Normally Normally Ope n Closed KI-00140E-10-14 N.O. N.C. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 51: Figure 37 - Terminate Auxiliary Output Ca8500B

    LE D ON = RELA Y with J1 Relay P ower E NE RGIZ ED set on ACU. TAMPER TB3 OCB-8 SWITCH Relays Normally Normally Closed Ope n N.C. N.O. RS-232 (COM4) KI-00141E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 52: S2 Dip Switches

    The following sub-sections outline S2 DIP switch functions and settings on door (CA) and elevator (EC) control boards. Keyscan factory defaults all control board settings prior to shipment. Depending on the installation however, you may have to reset various switches and reconfigure the control board for specific operating requirements.
  • Page 53 These settings are reserved for Keyscan hosted services. S2.11 & S2.12 – Software Selection The control board must be set on the corresponding Keyscan software platform – System VII, Vantage or Aurora. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 54: S2 Dip Switch Settings

    For direct serial communication connect to RS- 232 (COM4) - TB4 terminal block CB-485 and CPB-10-2 communication via CPB/CB MODULE (COM4) - H1 header NETCOMP communication plugged directly into M1 on control board (COM4) Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 55 200 ft/61 m between units and overall distance. Aurora and all current hardware products do not support modem communication. Ensure you are running the most current software version with this control board. For the latest software updates, visit www.keyscan.ca. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 56: Important - Circuit Board Function Revisions

    PC1097 and higher circuit boards are defaulted for 45,000 – Aurora - and 32,000 – System VII and Vantage - card-storage capacity – names not stored in ACU. Keyscan strongly advocates that either the dealer/installer or the end-user schedule automatic database backups at regular intervals to safeguard all site and cardholder data.
  • Page 57: S1 - System Reset / S3 - Restore Factory Defaults

    After the System Status LED has stopped flashing, the factory default settings have been restored and the Keyscan database has been cleared from the on-board memory. After Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 58: Figure 40 - S3 Restore Default Settings (Clear Memory) & S1 System Reset Locations

    Keyscan database is transferred to the control board’s on-board memory. If this is a new installation, enter the site information in the Keyscan Client software and then upload the Keyscan database information to the control board(s). Until you perform an upload from a Keyscan Client, the access control unit(s) will not function.
  • Page 59: Single Acu Communication

    If you are connecting a Keyscan legacy communication board – CPB-10-2, CB-485, CB-485M, or MC9600 modem – refer to the technical guide in the legacy folder on the Keyscan document CD or refer to the product installation document that was included with the product.
  • Page 60: Figure 41 - Rs-232 Data Cable Connections

    9 pin, RS-232, data cable, ensure that you follow the pin to wire colour assignments on the following diagram. When possible, use a Keyscan 9 pin, RS-232 data cable (Keyscan part # 40-2322) which is manufactured specifically for Keyscan serial data connectivity.
  • Page 61: Figure 42 - Communication - Direct Serial

    RS-232 (COM4) Shield* to ground lug Brown & White not used. Tape back separately. IOCB (COM1) * Insulate shield with PVC tubing such as Alpha (p/n PVC10516 16 AWG) or comparable insulator. KI-00153E-04-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 62: Figure 43 - Single Acu Communication - Usb Adaptor

    DIP switches 7 & 8 Black are OFF Green RS-232 (COM4) To ground lug IOCB (COM1) * Insulate shield with PVC tubing such as Alpha (p/n PVC10516 16 AWG) or comparable insulator. KI-00156E-04-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 63: Figure 44 - Communication - Netcom2P Or Netcom6P/Acu

    NETCOM2P or NETCOM6P plugged directly into the control board only supports a single panel communication loop. After installing and connecting the NETCOMP, ensure that the control board protective cover is re-affixed before applying power. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 64: Figure 45 - Communication - Netcom2 Or Netcom6

    If the NETCOM2 is mounted in the metal enclosure, the shield of the serial cable may be connected to GND as shown. If the NETCOM2 is mounted outside the metal enclosure, the shield must be insulated and connected directly to the metal enclosure ground lug. See Grounding Communication Cable Shield. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 65: Cim Communication

    I/Os)  CAN Bus 2 - CIM to CIM communication for CIM hardware control and monitoring and Keyscan’s reverse network communication Keyscan recommends CAN Bus 1 and CAN Bus 2 are connected on all CIM units.
  • Page 66: Cim Module Requirements

    Vantage – version 8.1.5 or higher for global inputs/outputs Note For global outputs, Keyscan recommends using the global OCB-8 option. This requires the purchase of an optional OCB-8, which connects to the control board’s Control 5 header. Global outputs are not supported on CA200 or CA250 door control units and EC1000, EC2000, EC1500, or EC2500 elevator control units.
  • Page 67: Bps/Can Bus Distance Chart

    3280 ft (1000 m) 100 ft (30 m) 19,200 3280 ft (1000 m) 49.2 ft (15 m) 57,600 984.25 ft (300 m) 26.2 ft (8 m) 115,200 262.46 ft (80 m) 9.84 ft (3 m) Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 68: Cim Jumper Settings

    PC or a network connection via a NETCOMP to the system communication software. Table 10 – CIM 0 – Jumper J4 Module Jumper # Jumper Setting Notes CIM 0 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 69: Table 11 - Cim Can Bus Termination Jumpers J5 - J8

    CIM unit to auto-match the ACU bit rate. The CIM unit automatically sets the CAN Bus bit rate to match. Keyscan recommends using the auto-match jumper setting. Table 12 – CIM Serial Bit Rate Jumpers J9 – J11...
  • Page 70: Cim Installation Guidelines

    The following guidelines offer a general outline for configuring and connecting the CIM units. You may have to refer to other Keyscan documentation that was included with other components such as a NETCOM2P or NETCOM6P – Reverse Network to complete the installation depending on how you are configuring the CIM units.
  • Page 71: Figure 48 - Cim To Acu Connections

    CAN1 150 mA CAN1 RESET SCKT1 COM2 Diag B3 B2 B1 B0 Power Good 1 2 1 2 1 2 1 2 Fault PC106x Rx - COM CAN - Tx (Flashing) KI-00264E-07-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 72: Figure 49 - Cim To Cim Canbus Connections

    White Blue RESET SCKT1 COM2 To earth ground Diag B3 B2 B1 B0 Power Good 1 2 1 2 1 2 1 2 Fault PC106x Rx - COM CAN - Tx (Flashing) KI-00265E-07-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 73: Serial Communication

    Serial communication is a direct serial connection from the PC to the CIM unit using a 9-pin RS-232 data cable with five (5) conductors - Keyscan part # 40-2322. A Communication Manager must be installed on the PC that has the direct serial connection to CIM 0.
  • Page 74: Network Communication Via Optional Netcom2P Or Netcom6P (Encrypted)

    0. This CIM unit must have a jumper on J4. Important The NETCOM2P and the NETCOM6P must be programmed with the Keyscan NETCOM Program Tool utility in order to function. Refer to the NETCOM2P/CIM or NETCOM6P/CIM Programming Guides for programming instructions.
  • Page 75: Figure 51 - Network Connection With Multiple Cims/Acu

    CAT 5 CAN Bus RESET SCKT1 Global Master Jumper ON - J3 Diag B3 B2 B1 B0 Power Good 1 2 1 2 1 2 1 2 PC106x Fault Rx-COM CAN-Tx KI-00461E-07-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 76: Network Communication Via Optional Netcom2 Or Netcom6 (Encrypted)

    0. This CIM unit must have a jumper on J4. Important The NETCOM2 must be programmed with the Keyscan NETCOM Program Tool utility in order to function. Refer to the NETCOM2 Programming Guide for programming instructions. Multiple Building Communication on a WAN Keyscan requires a point-to-point private network where NETCOMs are used on a LAN/WAN (TCP/IP) that integrates building-to-building communication for a non-reverse network application.
  • Page 77: Figure 52 - Network Connection With Netcom2 Or Netcom6 With Multiple Cims/Acus

    CAT 5 RESET CAN Bus SCKT1 Global Master Jumper ON - J3 Diag B3 B2 B1 B0 P ower Good 1 2 1 1 2 1 2 PC106x KI-00469E-10-14 Fault Rx-COM CAN -Tx Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 78: Cim Diagnostic Leds B3 - B0

    End of diagnostics routine is indicated when all four (4) LEDs flash three (3) times. Unless Power Good/Fault LED is flashing, the unit will not enter unit diagnostics mode even if a jumper is on J2. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 79: Figure 53 - Cim Diagnostic Leds - B3 - B0

    ACU quickly. The CIM may stay in this mode longer if it is auto- matching the bit rate of the ACU or is unable to communicate to the ACU via the global communication port.) Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 80: Power-Up & Test Voltages

    Each output is rated at 12 VDC – 1.2 Amperes. Before making any power connections at the ACU, Keyscan recommends that you use the following two tables and calculate the sum of the current demand for the devices drawing power from the ACU supply side and the RDR AUX supply side ensuring that you do not exceed the DPS-15’s current capacity.
  • Page 81: Table 14 - Acu Supply - Current Calculation Table

    Current Rating column that are to be powered from the AUX RDR supply on the DPS-15. Keyscan recommends a 200 mA reserve operating margin. The total current required from the AUX RDR supply should not exceed 1000 mA.
  • Page 82: System Power-Up

    ACUs after all correct voltage and current measurements are verified - refer to the Client on-line help Notes For battery circuit and auxiliary power output to function, two (2) transformers must be connected. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 83: Figure 54 - Power Supply Wiring

    AUX/RDR PC109x Control Board PSC1 CAS6105 Cable Use Keyscan p/n CAS6105 plug-in cable included with Connect to PSC1 DPS15 to connect control board with power supply. on control board. Diagram shows cut view of CA 8000 control board. The READER PWR PSC1 terminal is in the same location on all CA &...
  • Page 84: Control Board Voltage Test Points

    (+) 13.5 VDC ACU power after circuit protector (+) 5 VDC (+) 3.3 VDC Input Points Input points with open circuit (+) 5 VDC Input points shorted to common 0 VDC return Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 85: Figure 55 - Control Board Test Points - Voltages

    Figure 55 – Control Board Test Points – Voltages Cut View READER PWR PC109x Control Board FAIL Protective Cover FAIL ACU PWR Test Point Voltages TP1: +12V Reader TP2: +12V ACU TP3: +12V ACU Fused TP4: +5V TP5: +3.3V KI-00193E-04-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 86: Test Points - Communication Terminals

    TD is an ACU generated voltage (-) 10 VDC RD is a PC generated voltage Figure 56 – Control Board Communication Test Points Control Board (PC 109x) RS-232 (COM4) IOCB (COM1) KI-00194E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 87: Communication Diagnostics

    For CIM diagnostic LEDs, refer to page 78. Communication Status LEDs The CA250B, CA4500B, CA8500B, EC1500B, EC2500B, CB-485, and CPB-10-2 have communication LEDs for diagnostics and troubleshooting. The table below outlines the LED and its diagnostic function. When calling Keyscan technical support, indicating the LEDs state assists our technicians in isolating potential difficulties.
  • Page 88 LED states listed above are during normal CA or EC control board operation and do apply in other modes such clearing memory. COM4 LEDs functions are dependent on the configuration of S2 – switches 7 & 8. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 89: System Status Led

    The CA or EC control board’s last communication with the Client software was 3 minutes or greater. Green – solid The CA or EC control board has communicated to the Client software since its last system reset or clear memory. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 90: Card Diagnostics - Led Wiegand Bit Counters

    READER 3 READER 2 READER 1 Cut View of CA8500B CARD BITS Wiegand Bit Counter LEDs 10s 1s Protective ACU Cover COMMUNICATION STATUS TD1 RD1 TD2 RD2 TD3 RD3 TD4 RD4 KI-00147E-04-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 91: Appendix A - Keyscan & Hid Readers

    Appendix A – Keyscan & HID Readers Appendix A reviews typical connections for Keyscan and HID readers. Wiring diagrams are on the following pages. Refer to the appropriate diagram for specific reader connections. Be sure to use a cable that complies with the reader’s wiring specifications.
  • Page 92 See HID manual for operational details and recommendations. The following diagrams illustrate HID readers with dual LEDs. On models 5365, 5395, and Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 93 S16 – 5 OFF single LED = 06 C1 Beep When the pre-alert wire is connected to C1 (Beep) on the reader terminal, the reader will also sound on an “alarm tripped”. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 94: Figure 60 - Keyscan K-Prox2 (125 Khz)

    Relay Option in Technical Guide. Shield not connected. Isolate with electrical tape. 6 conductors - shielded 22 AWG Maximum 500 ft (152.4 m) Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00197E-08-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 95: Figure 61 - Keyscan K-Van Proximity Reader (125 Khz)

    Figure 61 – Keyscan K-VAN Proximity Reader (125 kHz) Orange wire not used. Isolate & tape back. Orange Blue used for pre-alert otherwise Shield not isolate and tape back. connected at If connecting external sound device, reader. see Pre-Alert Relay Option or refer to...
  • Page 96: Figure 62 - Keyscan K-Kpr Keypad / Proximity Reader (125 Khz)

    Figure 62 – Keyscan K-KPR Keypad / Proximity Reader (125 KHz) Diagram applies to PC109x or newer Keypad – 8 Bit Burst Format control board. For Rev 10 or older control boards, an optional KKI-KPR interface card is required. Orange wire not used.
  • Page 97: Figure 63 - Keyscan K-Smart Reader

    Maximum 500 ft (152.4 m) Shield not connected. May require 2 additional conductors Isolate with electrical tape. if using external pre-alert device. Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00200E-06-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 98: Figure 64 - Hid-5395 Wiring

    Maximum - 500 ft (152.4 m) Note - If Pre-alert is connected, the reader cannot read any HID 125 kHz-compatible card during the pre-alert beep. Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00201E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 99: Figure 65 - Hid 5365 / 6005 Wiring

    HID 125 kHz-compatible card during the pre-alert beep. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00202E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 100: Figure 66 - Hid 5355 Wiring

    Notes on HID 5355 The HID 5355 is suitable for indoor and outdoor use. Maximum read range at 12VDC – ProxCard II card is 9" (22 cm) – ISO ProxII card is 8" (20 cm). Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 101: Figure 67 - Hid 5375 Wiring

    HID 5375 operates at 12 VDC or 24 VDC. Refer to HID literature for correct jumper settings. If configured for 12 VDC, do not connect to 24 VDC power supply, otherwise damage to the reader circuit board will result. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 102: Figure 68 - Hid 5355Kp Wiring

    ACU Ground Shield Black separate DC power supply LED D1 (BEEP) Reader terminal on control board KI-00205E-07-11 Note on HID 5355 KP Reader/Keypad/LED ordered as 00 (4 bit burst) example 5355AGK00 (Red/Green colour) Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 103: Figure 69 - Hid Iclass Keyr10

    Maximum - 500 ft supply (152.4 m) Shield Rev. A Connections VDC + ACU Ground Shield Black LED D1 (BEEP) Reader terminal on control board LED D1 (BEEP) Reader terminal on control board KI-00206E-03-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 104: Figure 70 - Hid Iclass Keyr40

    6 conductors shielded 18 AWG Maximum - 500 ft (152.4 m) to separate DC power supply VDC + ACU Ground Shield Black LED D1 (BEEP) Reader terminal on control board KI-00207E-10-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 105: Figure 71 - Hid Iclass Keyrw400

    Shield not connected. - P1-5 Drain (Shield / Do not connect to Keyscan) Isolate with electrical - P1-6 Brown (Red LED / Do not connect to Keyscan) tape. - P1-7 Blue (Hold / do not connect to Keyscan) P2 Terminal...
  • Page 106: Figure 72 - Hid Iclass Keyrk40

    VDC + ACU Ground Shield Black LED D1 (BEEP) Reader terminal on control board KI-00209E-10-13 Note on HID iClass KEYRK40 Reader/Keypad/LED ordered as 00 (4 bit burst) – example 6131AKN00100 (Red/Green colour) Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 107: Figure 73 - Hid Iclass R90 Long Range Reader

    500 ft (152.4 m) maximum Terminal block on R90 reader ACU Ground Shield Black 1 Red + to separate power supply (3 Amp supply recommended) LED D1 (BEEP) Reader terminal on control board KI-00501E-03-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 108: Figure 74 - Hid Iclass R10 Series

    Shield not connected. Isolate with electrical tape. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) KI-00508E-10-13 Reader terminal on control board Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 109: Figure 75 - Hid Iclass R15 Series

    Shield not connected. Isolate with electrical tape. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) KI-00509E-10-13 Reader terminal on control board Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 110: Figure 76 - Hid Iclass R40 Series

    Shield not connected. Isolate with electrical tape. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) KI-00510E-10-13 Reader terminal on control board Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 111: Figure 77 - Hid Iclass Rk40 Series

    Shield not connected. Isolate with electrical tape. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) KI-00511E-10-13 Reader terminal on control board Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 112: Appendix B - Indala Readers

    Do not install readers in areas where broad spectrum EMI noise may be present. Devices such as motors, pumps, generators, and AC switching relays can create EMI noise. Readers mounted on a metal surface can reduce the read range. See the Indala manual for recommendations. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 113: Figure 78 - Indala Px 603 And Px 605 Wiring

    Isolate with electrical tape. ACU/OCB8 relay assignments. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) Reader terminal on control board KI-00210E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 114: Figure 79 - Indala Px610 Wiring

    Isolate with electrical tape. 6 conductors shielded 22 AWG 500 ft (152.4m ) maximum ACU Ground Shield Black 1 Red + separate power supply LED D1 (BEEP) Reader terminal on control board KI-00211E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 115: Figure 80 - Indala Px 620 Wiring

    The PX 620 is factory tuned. If a PX 620 requires tuning, tune only once. Excessive tuning may permanently damage the reader. Refer to the Indala documentation for instructions on tuning. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 116: Figure 81 - Indala Pxk 501 Wiring

    Maximum 500 ft (152.4 m) Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00213E-07-11 Note on Indala PXK 501 Wiring Reader/Keypad/LED ordered as 8 bit burst – example FP5061B-8 Bit Burst (Red only) Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 117: Appendix C - Wsskp-1 Keypad

    Appendix C – WSSKP-1 Keypad Appendix C reviews typical Keyscan WSSKP-1 keypad connections and keypad/reader combination connections. Table 22 – Keypad Power Specifications Reader Power Notes WSSKP-1 12 VDC, 20 mA Orange wire not connected. No digital output. WSSKP-1 12 VDC, 530 mA Orange wire connected.
  • Page 118: Figure 82 - Wsskp-1 Keypad Connection

    If using the orange wire, it is triggered from local PIN stored in keypad memory. The keypad memory stores 28 personal identification numbers (PIN). If orange wire is not used, tape back. See instructions with WSSKP-1 keypad for connections with third party devices. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 119: Figure 83 - Wsskp-1 Keypad/Reader Combination Connections

    Diagram Notes on WSSKP-1/Reader Combination The above diagram generally applies to a retro-fit where either a reader or keypad is already installed. Consider Keyscan’s K-KPR if a reader/keypad combination is required for a new installation. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 120: Appendix D - Wieex2

    Appendix D – WIEEX2 Appendix D reviews general information, installation guidelines, and connection diagrams for Keyscan RS485 Wiegand extenders (WIEEX2). Wiegand extenders are used on doors and readers that exceed the 500 feet maximum distance from the ACU. When installing the WIEEX2 extenders please check the version and observe the corresponding wiring diagram.
  • Page 121 6.00 or higher), connect RB4 on the receiver to the ‘normally closed’ position on the ACU lock relay. The WIEEX2 transmitter (TX) can control a lock device or relay to a maximum of 12 VDC, 500 mA. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 122: Figure 84 - Wiegand Extender Overview

    Figure 84 – Wiegand Extender Overview Reader Door Unlock Output Exit Device Door Contact Auxiliary Input Transmitter WIEEX2 -Tx Receiver WIEEX2 - Rx KI-00223E-06-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 123: Figure 85 - Wieex2 Rs485 Connections - (Firmware 6.00 Or Higher)

    J1 (shorted) on receiver to N.C. on lock relay. DC Supply 1 2 1 2 1 2 3 4 Door Exit Auxiliary Control Board Inputs Control Board Lock Relay Reader Terminal KI-00224E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 124: Figure 86 - Wieex2 To Ocb-8 Cable Connection

    Relay 4 to 8 – Not Used (set jumpers to reversed state) * Note on Relay 1 – To WIEEX-Rx eliminate relay chatter, Receiver remove jumper. Connect to GND RB4/RB5 with switch to change OCB-8 relay 2/3 connected on WIEEX-Tx KI-00226E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 125: Appendix E - Accessibility Hc Relay

    Door # /HC Relay # Ribbon Cable Connection OCB-8 to Control Board CA250B/OCB-8 Door 1/HC relay 5 Connect ribbon from OCB-8 to control 1 on CA250B Door 2/HC relay 6 Relay 7 and 8 reserved for Pre- alert. CA4500B/OCB-8 Door 1/HC relay 1 Connect ribbon on OCB-8 to control 4 on CA4500B.
  • Page 126: Figure 87 - Accessibility Hc Output Relay Ca250B/Ocb-8 Connections

    Figure 87 – Accessibility HC Output Relay CA250B/OCB-8 Connections doo r accessabi lity ope rato r CA250B Control OUTPUT KEYSCAN OCB-8 Boa rd CONTROL INC. BOARD When not use d a s Cut Vie w OCB8 HC outputs, rela y 5...
  • Page 127: Figure 88 - Accessibility Hc Output Relay Ca4500B/Ocb-8 Connections

    OCB-8 powere d through rib bon cable with J1 LE D ON = RELA Y Relay P ower set E NE RGIZ ED on ACU. doo r accessabi lity ope rato r KI-00228E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 128: Figure 89 - Accessibility Hc Output Relay Ca8500B/Ocb-8 Connections

    OCB-8 powere d through rib bon cable with J1 LE D ON = RELA Y Relay P ower set E NE RGIZ ED on ACU. doo r accessabi lity ope rato r KI-00229E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 129: Appendix F - Pre-Alert Relay

    Door 8 Important All relays on the OCB-8 board are dedicated as pre-alert output relays when used on the CA8500B circuit board. The pre-alert relay is also activated on an “alarm tripped”. Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 130: Figure 90 - Pre-Alert Relay Ca250B/Ocb-8 Connections

    Figure 90 – Pre-alert Relay CA250B/OCB-8 Connections Exte rnal pre-aler t device mounted at do or. DC Sup ply OUTPUT KEYSCAN CA250B CONTROL INC. BOARD Control Board OCB8 Not e Cut Vie w P C1102 DIP switches set RELAY rela ys for normal or REV.
  • Page 131: Figure 91 - Pre-Alert Relay Ca4500B/Ocb-8 Connections

    Switch 4) Power red stri pe OCB-8 powere d through rib bon LE D ON = cable with J1 RELA Y E NE RGIZ ED Relay P ower set on ACU. KI-00231E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 132: Figure 92 - Pre-Alert Relay Ca8500B/Ocb-8 Connections

    LE D ON = RELA Y cable with J1 Relay E NE RGIZ ED Power set on ACU. DC Sup ply Exte rnal pre-aler t device moun ted at door KI-00232E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 133: Appendix G - Global Output Relay

    Complete Global I/O Setup Instructions For complete instructions and requirements on configuring global inputs and outputs, refer to the Global Inputs & Outputs / Time Zones Setup Guide on the Keyscan documents CD. OCB-8/Global IO Assignments The following table outlines global output relay assignments on the OCB-8 and Client software. Please note the CA250 does not support global outputs.
  • Page 134: Figure 93 - Global Ocb-8 Ribbon Cable Connection With Ca4500 & Ca8500

    OCB-8 powere d through rib bon LE D ON = cable with J1 Relay RELA Y E NE RGIZ ED Power set on ACU. to o utp ut (alar m/CCTV etc.) KI-00475E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 135: Current Ratings

    Use the current calculation worksheet on the next page for determining power supply requirements. Ratings are based on 12 VDC. Do not exceed the recommended operating maximum of a power supply. See tables for Keyscan, HID and Indala reader voltage/current ratings.
  • Page 136: Relay States

    Aux Output Reversed Relay Aux Output Reversed Relay Pre-alert Relay Normal Activated Pre-alert Relay Normal Normal Pre-alert Relay Reversed Activated Pre-alert Relay Reversed Normal Accessibility Normal Activated Relay Accessibility Normal Normal Relay Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 137 Manual Output Control – Aux Status Off (Red) Manual Output Control – Aux Status On (Green) Relay State Open Relay State Closed OCB8 – Relay Jumper in Normal Position OCB8 – Relay Jumper in Reversed Position Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 138: Warranty

    Seller’s Right of Possession In addition to all remedies Keyscan may possess, Keyscan shall have the right at any time for credit reasons or because of buyer’s defaults, to withhold shipments in whole or in part, to recall goods in transit, retake same and repossess all goods, which may be stored, without the necessity of taking any other action.
  • Page 139: Index

    16 enclosure door hardware, 27 dimensions, 16 main circuit boards, 84 power supply, 20 enclosure ground strap readers, 30 connecting, 26 exit buttons, 29 Wiegand bit counter LEDs, 90 Keyscan Inc. – Technical Guide (PC109x - 04.15)
  • Page 140 Wiegand Extenders (WIEEX), Keyscan Inc. – Technical Guide (PC109x - 04.15)