Page 2
Information and specifications in this document are subject to change without notice. Except for the benefit of installation and operation of the Keyscan access control system, no part of this documentation may be reproduced or transmitted in any form or by any means without the expressed written permission of Keyscan Inc.
OCB-8 Relay Board ........................31 Terminate Lock Wiring ........................31 Terminate Input Wiring ........................ 37 Terminate Elevator Floor Wiring ..................... 43 Terminate Reader Wiring at ACU....................47 Terminate Auxiliary Outputs with Hardware/Alarms................49 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Page 5
Communication Status LEDs ......................87 System Status LED ........................89 Card Diagnostics - LED Wiegand Bit Counters .................. 90 Appendix A – Keyscan & HID Readers ..................... 91 Power Specifications ........................91 Appendix B – Indala Readers ......................112 Power Specifications ........................112 Appendix C –...
Page 6
Appendix F – Pre-alert Relay ......................129 Pre-alert ............................ 129 Appendix G – Global Output Relay ....................133 OCB-8/Global IO Assignments ...................... 133 Current Ratings ..........................135 Relay States ..........................136 Warranty ............................138 Index ............................139 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Foreword Keyscan systems are designed for use in various environments and applications. As such, ensure correct cable, power, ground, and environment specifications are followed for reliable and safe operation of the equipment. Approved Standards Keyscan CA250, CA4500, CA8500, EC1500 and EC2500 series control units conform to the following approved standards: ...
We recommend having the following tools on hand to install the access control system: Digital voltmeter Wire cutters & needle nose pliers Soldering iron & tape Set of screwdrivers Drill & drill bits Laptop computer (optional) Keyscan Inc. – Technical Guide (PC109x - 04.15)
Failing to ground the shields or using incorrect cables may cause noise or interference and result in improper card reads. Important Ensure the chassis ground (GND) on the DPS-15 is connected to the metal enclosure ground lug. Keyscan Inc. – Technical Guide (PC109x - 04.15)
ACU 3 KEYSCAN RS232 Tape Earth back shield Tape DPS15 back Control Board shield 40-2322 Data Cable ** RS-232 connections at EGND CIM 0 do not apply when using a NETCOM2P/6P. KI-00470E-07-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
2 x 16V 40VA transformers or 2 x 16.5V 37VA transformers are connected to the Keyscan DPS-15 power supply locate the transformers within 30 feet (9.144 m) of the Keyscan DPS-15 power supply - do not mount the transformers inside the ACU metal enclosure ...
Rev 11, Rev 10 & Rev 9 Control Boards If installing a Rev.11, Rev.10, or Rev. 9 control board in a metal enclosure with the pre-mounted metal standoffs, you require an adaptor kit - P/N – AK2005. Keyscan Inc. – Technical Guide (PC109x - 04.15)
Mounting the DPS-15 Power Supply The Keyscan DPS-15 is a 13.5 VDC dual linear regulated power supply for powering the ACU circuit boards and the readers with the following outputs: ACU output 12 VDC @ 1.2 Amperes AUX/RDR output 12 VDC @ 1.2 Amperes...
Figure 6 – Mounting Power Supplies Hex Nuts x 2 Top of ACU Enclosure Bolts x 2 Top mount location for DPS-15 power supply with CAS6105 plug-in cable to PSC1 terminal. Control Board KI-00107E-06-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
When terminating the communication cable in the metal enclosure, ensure that the shield is insulated and connected to the ground lug. Keyscan suggests Alpha PVC 10516 – 16 AWG clear tubing or a comparable tubing to insulate the shield. Do not connect the shield to GND on a communication terminal block.
Metal PC109x Enclosure Control Board Connect the yellow wires on the tamper switch to TB3 terminal on the control board. Cut View Protective Cover TAMPER TB3 SWITCH Tamper Switch RS-232 (COM4) KI-00116E-04-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
3/4" conduit to exit to ACU Door contact 1 pair 18 AWG Mag Lock 6 conductors shielded 22 or 18 AWG Reader KEYSCAN Door Strike 36" to 48" (91.4 to 121.9 cm) KI-00119E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Permits may be required before installing magnetic locks. Use a battery for temporary power to ensure the door operates properly – alignment, holding, activation, de- activation – before connecting to the Keyscan access control unit. Figure 16 – Typical Door Strike Connection KI-00120E-07-11 Figure 17 –...
Determines the amount of Lens time the output relays will energize when motion is detected. (RTE - Request To Exit) Auxiliary Input Aux Input NO = Normally Open NC = Normally Closed KI-00122E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
For mounting readers to a metal surface, consult with the manufacturer's documentation. If a door/reader is located beyond the maximum cable length to the ACU, use a Keyscan WIEEX2 extender kit to a maximum distance of 4000 feet (1219.2 m).
The following sub-sections review terminating lock, input, elevator, reader, and auxiliary output wiring at the access control units. OCB-8 Relay Board Keyscan’s OCB-8 relay board is used for terminating door locks, magnetic locks, elevator relays, and alarm/auxiliary outputs at the access control unit. Table 3 – OCB-8 Specifications...
Page 32
Relay output and DIP switch assignments are noted on the OCB-8 diagrams on the succeeding pages. Keyscan access control units include diodes, Install diodes across all DC door strikes as shown in Figure 23 on page 35. The cathode of the diode connects to the positive side of the strike at the door. The anode of the diode connects to the common return wire.
Figure 21 – Lock State - Fail Secure Device 'Normally Open' Relay board positon on relay Door Strike to common on DC power supply supply Lock State Lock Supply Fail Secure Device KI-00125E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Figure 22 – Terminate Lock Wiring CA250B When OCB-8 connected to CA250B Relay 5 = Aux Output 3 or HC Output 1 Relay 6 = Aux Output 4 or HC Output 2 Do not use relays for both functions. CA250B...
- Fail Safe – to N.C. Ensure all lock ha rdware Diode complies with fed eral, 1N400 4 N.C. state/provincial, and municipal fire cod es. Gro und Lug DC Sup ply KI-00127E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Ensure all lock - Fail Secure - hard wa re complie s to N.O. with federa l, state/ Diode provincial, and 1N400 4 12 VDC+ municipal fire cod es. Gro und KI-00128E-10-14 Sup ply Keyscan Inc. – Technical Guide (PC109x - 04.15)
Examples of exit devices are exit push buttons or motion sensors (PIR) etc. Keyscan recommends a PIR with a pulse output of 1/2 second and suitable for its environment. Security Monitoring Connections A normally-closed device may be connected to an auxiliary alarm input for monitoring stairwell or interior doors, or windows.
AUX Inputs - E Notes Diagram illustrates CA8500B. Connections also apply to CA250B & CA4500B. - CA250B – up to 2 door inputs Door 1 - CA4500B – up to 4 door inputs Non-supervised - CA8500B – up to 8 door inputs Supervision level set in Client software: System VII &...
Push Button Diagram illustrates CA8500B. Connections also apply to CA250B & CA4500B. - CA250B – up to 2 Request To Exits - CA4500B – up to 4 Request To Exits - CA8500B – up to 8 Request To Exits NO = Normally Open...
Diagram illustrates CA8500B. Connections also apply to NO = Normally Open CA250B & CA4500B. - CA250B – up to 2 Request to Exits - CA4500B – up to 4 Request to Exits Non-supervised - CA8500B – up to 8 Request to Exits...
Notes Diagram illustrates CA8500B. Connections Lens also apply to CA250B & CA4500B. - CA250B – up to 2 Request to Exits PIR (Request To Exit) - CA450B – up to 4 Request to Exits No supervision - CA8500B – up to 8 Request to Exits...
NC = Normally Closed Connections also apply to CA250B & CA4500B. - CA250B – up to 8 Supervised Auxiliary Alarm Inputs - CA4500B – up to 16 Supervised Auxiliary Alarm Inputs - CA8500B – up to 16 Supervised Auxiliary Inputs...
Fire Panel * OCB-8s must be purchased separately. trips on alarm Ensure all elevator hardware complies with all fire code regulations. N.C. AUX 12 V or ACU 12 V on DPS-15 KI-00134E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Fire Panel * OCB-8s must be purchased separately. trips on alarm Ensure all elevator hardware complies with all fire code regulations. N.C. AUX 12 V or ACU 12 V on DPS-15 KI-00135E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Green – Data output bit 0 White – Data output bit 1 Blue – Optional pre-alert (reader beeper) For specific reader wiring review the appendices listed in the Table of Contents. Keyscan Inc. – Technical Guide (PC109x - 04.15)
AC Fail EGND N.C. DC Output 12V Ground Shield External DC Supply READER PWR FAIL LED D1 (BEEP) FAIL ACU PWR Reader terminal on control board Power terminal on control board KI-00138E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Do not assign a time zone to an auxiliary output if the output has previously been assigned to an alarm event. The alarm has priority over the time zone. Figure 35 – Terminate Auxiliary Outputs CA250B When OCB-8 connected to CA250B...
LE D ON = RELA Y cable with J1 E NE RGIZ ED Relay P ower set on ACU. OCB-8 RS-232 (COM4) OCB-8 Relays Normally Normally Ope n Closed KI-00140E-10-14 N.O. N.C. Keyscan Inc. – Technical Guide (PC109x - 04.15)
LE D ON = RELA Y with J1 Relay P ower E NE RGIZ ED set on ACU. TAMPER TB3 OCB-8 SWITCH Relays Normally Normally Closed Ope n N.C. N.O. RS-232 (COM4) KI-00141E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
The following sub-sections outline S2 DIP switch functions and settings on door (CA) and elevator (EC) control boards. Keyscan factory defaults all control board settings prior to shipment. Depending on the installation however, you may have to reset various switches and reconfigure the control board for specific operating requirements.
Page 53
These settings are reserved for Keyscan hosted services. S2.11 & S2.12 – Software Selection The control board must be set on the corresponding Keyscan software platform – System VII, Vantage or Aurora. Keyscan Inc. – Technical Guide (PC109x - 04.15)
For direct serial communication connect to RS- 232 (COM4) - TB4 terminal block CB-485 and CPB-10-2 communication via CPB/CB MODULE (COM4) - H1 header NETCOMP communication plugged directly into M1 on control board (COM4) Keyscan Inc. – Technical Guide (PC109x - 04.15)
Page 55
200 ft/61 m between units and overall distance. Aurora and all current hardware products do not support modem communication. Ensure you are running the most current software version with this control board. For the latest software updates, visit www.keyscan.ca. Keyscan Inc. – Technical Guide (PC109x - 04.15)
PC1097 and higher circuit boards are defaulted for 45,000 – Aurora - and 32,000 – System VII and Vantage - card-storage capacity – names not stored in ACU. Keyscan strongly advocates that either the dealer/installer or the end-user schedule automatic database backups at regular intervals to safeguard all site and cardholder data.
After the System Status LED has stopped flashing, the factory default settings have been restored and the Keyscan database has been cleared from the on-board memory. After Keyscan Inc. – Technical Guide (PC109x - 04.15)
Keyscan database is transferred to the control board’s on-board memory. If this is a new installation, enter the site information in the Keyscan Client software and then upload the Keyscan database information to the control board(s). Until you perform an upload from a Keyscan Client, the access control unit(s) will not function.
If you are connecting a Keyscan legacy communication board – CPB-10-2, CB-485, CB-485M, or MC9600 modem – refer to the technical guide in the legacy folder on the Keyscan document CD or refer to the product installation document that was included with the product.
9 pin, RS-232, data cable, ensure that you follow the pin to wire colour assignments on the following diagram. When possible, use a Keyscan 9 pin, RS-232 data cable (Keyscan part # 40-2322) which is manufactured specifically for Keyscan serial data connectivity.
RS-232 (COM4) Shield* to ground lug Brown & White not used. Tape back separately. IOCB (COM1) * Insulate shield with PVC tubing such as Alpha (p/n PVC10516 16 AWG) or comparable insulator. KI-00153E-04-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
DIP switches 7 & 8 Black are OFF Green RS-232 (COM4) To ground lug IOCB (COM1) * Insulate shield with PVC tubing such as Alpha (p/n PVC10516 16 AWG) or comparable insulator. KI-00156E-04-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
NETCOM2P or NETCOM6P plugged directly into the control board only supports a single panel communication loop. After installing and connecting the NETCOMP, ensure that the control board protective cover is re-affixed before applying power. Keyscan Inc. – Technical Guide (PC109x - 04.15)
If the NETCOM2 is mounted in the metal enclosure, the shield of the serial cable may be connected to GND as shown. If the NETCOM2 is mounted outside the metal enclosure, the shield must be insulated and connected directly to the metal enclosure ground lug. See Grounding Communication Cable Shield. Keyscan Inc. – Technical Guide (PC109x - 04.15)
I/Os) CAN Bus 2 - CIM to CIM communication for CIM hardware control and monitoring and Keyscan’s reverse network communication Keyscan recommends CAN Bus 1 and CAN Bus 2 are connected on all CIM units.
Vantage – version 8.1.5 or higher for global inputs/outputs Note For global outputs, Keyscan recommends using the global OCB-8 option. This requires the purchase of an optional OCB-8, which connects to the control board’s Control 5 header. Global outputs are not supported on CA200 or CA250 door control units and EC1000, EC2000, EC1500, or EC2500 elevator control units.
3280 ft (1000 m) 100 ft (30 m) 19,200 3280 ft (1000 m) 49.2 ft (15 m) 57,600 984.25 ft (300 m) 26.2 ft (8 m) 115,200 262.46 ft (80 m) 9.84 ft (3 m) Keyscan Inc. – Technical Guide (PC109x - 04.15)
PC or a network connection via a NETCOMP to the system communication software. Table 10 – CIM 0 – Jumper J4 Module Jumper # Jumper Setting Notes CIM 0 Keyscan Inc. – Technical Guide (PC109x - 04.15)
CIM unit to auto-match the ACU bit rate. The CIM unit automatically sets the CAN Bus bit rate to match. Keyscan recommends using the auto-match jumper setting. Table 12 – CIM Serial Bit Rate Jumpers J9 – J11...
The following guidelines offer a general outline for configuring and connecting the CIM units. You may have to refer to other Keyscan documentation that was included with other components such as a NETCOM2P or NETCOM6P – Reverse Network to complete the installation depending on how you are configuring the CIM units.
Serial communication is a direct serial connection from the PC to the CIM unit using a 9-pin RS-232 data cable with five (5) conductors - Keyscan part # 40-2322. A Communication Manager must be installed on the PC that has the direct serial connection to CIM 0.
0. This CIM unit must have a jumper on J4. Important The NETCOM2P and the NETCOM6P must be programmed with the Keyscan NETCOM Program Tool utility in order to function. Refer to the NETCOM2P/CIM or NETCOM6P/CIM Programming Guides for programming instructions.
0. This CIM unit must have a jumper on J4. Important The NETCOM2 must be programmed with the Keyscan NETCOM Program Tool utility in order to function. Refer to the NETCOM2 Programming Guide for programming instructions. Multiple Building Communication on a WAN Keyscan requires a point-to-point private network where NETCOMs are used on a LAN/WAN (TCP/IP) that integrates building-to-building communication for a non-reverse network application.
End of diagnostics routine is indicated when all four (4) LEDs flash three (3) times. Unless Power Good/Fault LED is flashing, the unit will not enter unit diagnostics mode even if a jumper is on J2. Keyscan Inc. – Technical Guide (PC109x - 04.15)
ACU quickly. The CIM may stay in this mode longer if it is auto- matching the bit rate of the ACU or is unable to communicate to the ACU via the global communication port.) Keyscan Inc. – Technical Guide (PC109x - 04.15)
Each output is rated at 12 VDC – 1.2 Amperes. Before making any power connections at the ACU, Keyscan recommends that you use the following two tables and calculate the sum of the current demand for the devices drawing power from the ACU supply side and the RDR AUX supply side ensuring that you do not exceed the DPS-15’s current capacity.
Current Rating column that are to be powered from the AUX RDR supply on the DPS-15. Keyscan recommends a 200 mA reserve operating margin. The total current required from the AUX RDR supply should not exceed 1000 mA.
ACUs after all correct voltage and current measurements are verified - refer to the Client on-line help Notes For battery circuit and auxiliary power output to function, two (2) transformers must be connected. Keyscan Inc. – Technical Guide (PC109x - 04.15)
AUX/RDR PC109x Control Board PSC1 CAS6105 Cable Use Keyscan p/n CAS6105 plug-in cable included with Connect to PSC1 DPS15 to connect control board with power supply. on control board. Diagram shows cut view of CA 8000 control board. The READER PWR PSC1 terminal is in the same location on all CA &...
(+) 13.5 VDC ACU power after circuit protector (+) 5 VDC (+) 3.3 VDC Input Points Input points with open circuit (+) 5 VDC Input points shorted to common 0 VDC return Keyscan Inc. – Technical Guide (PC109x - 04.15)
TD is an ACU generated voltage (-) 10 VDC RD is a PC generated voltage Figure 56 – Control Board Communication Test Points Control Board (PC 109x) RS-232 (COM4) IOCB (COM1) KI-00194E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
For CIM diagnostic LEDs, refer to page 78. Communication Status LEDs The CA250B, CA4500B, CA8500B, EC1500B, EC2500B, CB-485, and CPB-10-2 have communication LEDs for diagnostics and troubleshooting. The table below outlines the LED and its diagnostic function. When calling Keyscan technical support, indicating the LEDs state assists our technicians in isolating potential difficulties.
Page 88
LED states listed above are during normal CA or EC control board operation and do apply in other modes such clearing memory. COM4 LEDs functions are dependent on the configuration of S2 – switches 7 & 8. Keyscan Inc. – Technical Guide (PC109x - 04.15)
The CA or EC control board’s last communication with the Client software was 3 minutes or greater. Green – solid The CA or EC control board has communicated to the Client software since its last system reset or clear memory. Keyscan Inc. – Technical Guide (PC109x - 04.15)
Appendix A – Keyscan & HID Readers Appendix A reviews typical connections for Keyscan and HID readers. Wiring diagrams are on the following pages. Refer to the appropriate diagram for specific reader connections. Be sure to use a cable that complies with the reader’s wiring specifications.
Page 92
See HID manual for operational details and recommendations. The following diagrams illustrate HID readers with dual LEDs. On models 5365, 5395, and Keyscan Inc. – Technical Guide (PC109x - 04.15)
Page 93
S16 – 5 OFF single LED = 06 C1 Beep When the pre-alert wire is connected to C1 (Beep) on the reader terminal, the reader will also sound on an “alarm tripped”. Keyscan Inc. – Technical Guide (PC109x - 04.15)
Relay Option in Technical Guide. Shield not connected. Isolate with electrical tape. 6 conductors - shielded 22 AWG Maximum 500 ft (152.4 m) Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00197E-08-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Figure 61 – Keyscan K-VAN Proximity Reader (125 kHz) Orange wire not used. Isolate & tape back. Orange Blue used for pre-alert otherwise Shield not isolate and tape back. connected at If connecting external sound device, reader. see Pre-Alert Relay Option or refer to...
Figure 62 – Keyscan K-KPR Keypad / Proximity Reader (125 KHz) Diagram applies to PC109x or newer Keypad – 8 Bit Burst Format control board. For Rev 10 or older control boards, an optional KKI-KPR interface card is required. Orange wire not used.
Maximum 500 ft (152.4 m) Shield not connected. May require 2 additional conductors Isolate with electrical tape. if using external pre-alert device. Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00200E-06-12 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Maximum - 500 ft (152.4 m) Note - If Pre-alert is connected, the reader cannot read any HID 125 kHz-compatible card during the pre-alert beep. Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00201E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
HID 125 kHz-compatible card during the pre-alert beep. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00202E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Notes on HID 5355 The HID 5355 is suitable for indoor and outdoor use. Maximum read range at 12VDC – ProxCard II card is 9" (22 cm) – ISO ProxII card is 8" (20 cm). Keyscan Inc. – Technical Guide (PC109x - 04.15)
HID 5375 operates at 12 VDC or 24 VDC. Refer to HID literature for correct jumper settings. If configured for 12 VDC, do not connect to 24 VDC power supply, otherwise damage to the reader circuit board will result. Keyscan Inc. – Technical Guide (PC109x - 04.15)
ACU Ground Shield Black separate DC power supply LED D1 (BEEP) Reader terminal on control board KI-00205E-07-11 Note on HID 5355 KP Reader/Keypad/LED ordered as 00 (4 bit burst) example 5355AGK00 (Red/Green colour) Keyscan Inc. – Technical Guide (PC109x - 04.15)
Maximum - 500 ft supply (152.4 m) Shield Rev. A Connections VDC + ACU Ground Shield Black LED D1 (BEEP) Reader terminal on control board LED D1 (BEEP) Reader terminal on control board KI-00206E-03-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
6 conductors shielded 18 AWG Maximum - 500 ft (152.4 m) to separate DC power supply VDC + ACU Ground Shield Black LED D1 (BEEP) Reader terminal on control board KI-00207E-10-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Shield not connected. - P1-5 Drain (Shield / Do not connect to Keyscan) Isolate with electrical - P1-6 Brown (Red LED / Do not connect to Keyscan) tape. - P1-7 Blue (Hold / do not connect to Keyscan) P2 Terminal...
VDC + ACU Ground Shield Black LED D1 (BEEP) Reader terminal on control board KI-00209E-10-13 Note on HID iClass KEYRK40 Reader/Keypad/LED ordered as 00 (4 bit burst) – example 6131AKN00100 (Red/Green colour) Keyscan Inc. – Technical Guide (PC109x - 04.15)
500 ft (152.4 m) maximum Terminal block on R90 reader ACU Ground Shield Black 1 Red + to separate power supply (3 Amp supply recommended) LED D1 (BEEP) Reader terminal on control board KI-00501E-03-13 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Shield not connected. Isolate with electrical tape. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) KI-00508E-10-13 Reader terminal on control board Keyscan Inc. – Technical Guide (PC109x - 04.15)
Shield not connected. Isolate with electrical tape. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) KI-00509E-10-13 Reader terminal on control board Keyscan Inc. – Technical Guide (PC109x - 04.15)
Shield not connected. Isolate with electrical tape. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) KI-00510E-10-13 Reader terminal on control board Keyscan Inc. – Technical Guide (PC109x - 04.15)
Shield not connected. Isolate with electrical tape. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) KI-00511E-10-13 Reader terminal on control board Keyscan Inc. – Technical Guide (PC109x - 04.15)
Do not install readers in areas where broad spectrum EMI noise may be present. Devices such as motors, pumps, generators, and AC switching relays can create EMI noise. Readers mounted on a metal surface can reduce the read range. See the Indala manual for recommendations. Keyscan Inc. – Technical Guide (PC109x - 04.15)
Isolate with electrical tape. ACU/OCB8 relay assignments. 6 conductors shielded 22 AWG Maximum - 500 ft (152.4 m) ACU Ground Shield LED D1 (BEEP) Reader terminal on control board KI-00210E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Isolate with electrical tape. 6 conductors shielded 22 AWG 500 ft (152.4m ) maximum ACU Ground Shield Black 1 Red + separate power supply LED D1 (BEEP) Reader terminal on control board KI-00211E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
The PX 620 is factory tuned. If a PX 620 requires tuning, tune only once. Excessive tuning may permanently damage the reader. Refer to the Indala documentation for instructions on tuning. Keyscan Inc. – Technical Guide (PC109x - 04.15)
Maximum 500 ft (152.4 m) Shield Ground LED D1 (BEEP) Reader terminal on control board KI-00213E-07-11 Note on Indala PXK 501 Wiring Reader/Keypad/LED ordered as 8 bit burst – example FP5061B-8 Bit Burst (Red only) Keyscan Inc. – Technical Guide (PC109x - 04.15)
Appendix C – WSSKP-1 Keypad Appendix C reviews typical Keyscan WSSKP-1 keypad connections and keypad/reader combination connections. Table 22 – Keypad Power Specifications Reader Power Notes WSSKP-1 12 VDC, 20 mA Orange wire not connected. No digital output. WSSKP-1 12 VDC, 530 mA Orange wire connected.
If using the orange wire, it is triggered from local PIN stored in keypad memory. The keypad memory stores 28 personal identification numbers (PIN). If orange wire is not used, tape back. See instructions with WSSKP-1 keypad for connections with third party devices. Keyscan Inc. – Technical Guide (PC109x - 04.15)
Diagram Notes on WSSKP-1/Reader Combination The above diagram generally applies to a retro-fit where either a reader or keypad is already installed. Consider Keyscan’s K-KPR if a reader/keypad combination is required for a new installation. Keyscan Inc. – Technical Guide (PC109x - 04.15)
Appendix D – WIEEX2 Appendix D reviews general information, installation guidelines, and connection diagrams for Keyscan RS485 Wiegand extenders (WIEEX2). Wiegand extenders are used on doors and readers that exceed the 500 feet maximum distance from the ACU. When installing the WIEEX2 extenders please check the version and observe the corresponding wiring diagram.
Page 121
6.00 or higher), connect RB4 on the receiver to the ‘normally closed’ position on the ACU lock relay. The WIEEX2 transmitter (TX) can control a lock device or relay to a maximum of 12 VDC, 500 mA. Keyscan Inc. – Technical Guide (PC109x - 04.15)
J1 (shorted) on receiver to N.C. on lock relay. DC Supply 1 2 1 2 1 2 3 4 Door Exit Auxiliary Control Board Inputs Control Board Lock Relay Reader Terminal KI-00224E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Relay 4 to 8 – Not Used (set jumpers to reversed state) * Note on Relay 1 – To WIEEX-Rx eliminate relay chatter, Receiver remove jumper. Connect to GND RB4/RB5 with switch to change OCB-8 relay 2/3 connected on WIEEX-Tx KI-00226E-07-11 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Door # /HC Relay # Ribbon Cable Connection OCB-8 to Control Board CA250B/OCB-8 Door 1/HC relay 5 Connect ribbon from OCB-8 to control 1 on CA250B Door 2/HC relay 6 Relay 7 and 8 reserved for Pre- alert. CA4500B/OCB-8 Door 1/HC relay 1 Connect ribbon on OCB-8 to control 4 on CA4500B.
Figure 87 – Accessibility HC Output Relay CA250B/OCB-8 Connections doo r accessabi lity ope rato r CA250B Control OUTPUT KEYSCAN OCB-8 Boa rd CONTROL INC. BOARD When not use d a s Cut Vie w OCB8 HC outputs, rela y 5...
OCB-8 powere d through rib bon cable with J1 LE D ON = RELA Y Relay P ower set E NE RGIZ ED on ACU. doo r accessabi lity ope rato r KI-00228E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
OCB-8 powere d through rib bon cable with J1 LE D ON = RELA Y Relay P ower set E NE RGIZ ED on ACU. doo r accessabi lity ope rato r KI-00229E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Door 8 Important All relays on the OCB-8 board are dedicated as pre-alert output relays when used on the CA8500B circuit board. The pre-alert relay is also activated on an “alarm tripped”. Keyscan Inc. – Technical Guide (PC109x - 04.15)
Figure 90 – Pre-alert Relay CA250B/OCB-8 Connections Exte rnal pre-aler t device mounted at do or. DC Sup ply OUTPUT KEYSCAN CA250B CONTROL INC. BOARD Control Board OCB8 Not e Cut Vie w P C1102 DIP switches set RELAY rela ys for normal or REV.
Switch 4) Power red stri pe OCB-8 powere d through rib bon LE D ON = cable with J1 RELA Y E NE RGIZ ED Relay P ower set on ACU. KI-00231E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
LE D ON = RELA Y cable with J1 Relay E NE RGIZ ED Power set on ACU. DC Sup ply Exte rnal pre-aler t device moun ted at door KI-00232E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Complete Global I/O Setup Instructions For complete instructions and requirements on configuring global inputs and outputs, refer to the Global Inputs & Outputs / Time Zones Setup Guide on the Keyscan documents CD. OCB-8/Global IO Assignments The following table outlines global output relay assignments on the OCB-8 and Client software. Please note the CA250 does not support global outputs.
OCB-8 powere d through rib bon LE D ON = cable with J1 Relay RELA Y E NE RGIZ ED Power set on ACU. to o utp ut (alar m/CCTV etc.) KI-00475E-10-14 Keyscan Inc. – Technical Guide (PC109x - 04.15)
Use the current calculation worksheet on the next page for determining power supply requirements. Ratings are based on 12 VDC. Do not exceed the recommended operating maximum of a power supply. See tables for Keyscan, HID and Indala reader voltage/current ratings.
Aux Output Reversed Relay Aux Output Reversed Relay Pre-alert Relay Normal Activated Pre-alert Relay Normal Normal Pre-alert Relay Reversed Activated Pre-alert Relay Reversed Normal Accessibility Normal Activated Relay Accessibility Normal Normal Relay Keyscan Inc. – Technical Guide (PC109x - 04.15)
Page 137
Manual Output Control – Aux Status Off (Red) Manual Output Control – Aux Status On (Green) Relay State Open Relay State Closed OCB8 – Relay Jumper in Normal Position OCB8 – Relay Jumper in Reversed Position Keyscan Inc. – Technical Guide (PC109x - 04.15)
Seller’s Right of Possession In addition to all remedies Keyscan may possess, Keyscan shall have the right at any time for credit reasons or because of buyer’s defaults, to withhold shipments in whole or in part, to recall goods in transit, retake same and repossess all goods, which may be stored, without the necessity of taking any other action.