Terminate Input Wiring

The following sub-headings review termination of door contacts, exit, and auxiliary alarm input wiring.
Door Monitoring Connections
A normally-closed door contact is for monitoring door security. Door inputs are shunted during the door relay
unlock time.
Figure 36 – Terminate Input Wiring – Door Inputs (Contacts)
Door Inputs - A
Common
1
2
3
4
5
6
7
8
NC
COM
Door 1
Supervision level set in Client software:
System VII & Vantage – Site Unit Setup
Aurora – Hardware Setup
Supervision level applied to all door inputs, RTE inputs, and auxiliary inputs.
Single end of line
supervision
KI-00129E-10-13
Keyscan Inc. – Technical Guide (PC109x - 07.15)
Cut View of CA8500B
RTE Inputs - B
Common
AUX Inputs - C
1
2
3
4
5
8
1
2
3
4
6
7
Notes
Diagram illustrates CA8500B. Connections
also apply to CA250B & CA4500B.
- CA250B – up to 2 door inputs
- CA4500B – up to 4 door inputs
Non-supervised
- CA8500B – up to 8 door inputs
to
Door
Input
1K
NC
COM
Door Contact
1
Double end of line
to Door Input
supervision
1K
1
Common
AUX Inputs - D
5
8
9
10
11
12
13
16
6
7
14
15
to
Common
to Common
3K
NC
COM
Door Contact
Common
AUX Inputs - E
17
18
19
20
21
24
22
23
55