Proline Promag P 200
Terminal assignment
Supply voltage
Endress+Hauser
HART load
Dynamic variables
Power supply
Transmitter
4-20 mA HART connection version with additional outputs
2
1
Maximum number of terminals, without integrated overvoltage
protection
1
Output 1 (passive): supply voltage and signal transmission
2
Output 2 (passive): supply voltage and signal transmission
3
Ground terminal for cable shield
Order code for
"Output"
Option A
Option B
1)
1)
Output 1 must always be used; output 2 is optional.
An external power supply is required for each output. The following supply voltage values apply for the 4-20
mA HART current output:
Order code for
"Output"
• Option A: 4-20 mA HART
• Option B: 4-20 mA HART, pulse/
frequency/switch output
• Min. 250 Ω
• Max.500 W
The measured variables can be freely assigned to the dynamic variables.
Measured variables for PV (primary dynamic variable)
• Volume flow
• Mass flow
Measured variables for SV, TV, QV (secondary, tertiary and quaternary
dynamic variable)
• Volume flow
• Mass flow
• Totalizer 1
• Totalizer 2
• Totalizer 3
3
A0013570
Maximum number of terminals, with integrated
overvoltage protection
Output 1
1 (+)
2 (-)
4-20 mA HART (passive)
4-20 mA HART (passive)
Minimum terminal voltage
For 4 mA: ³ DC18 V
For 20 mA: ³ DC14 V
2
1
Terminal numbers
Output 2
3 (+)
-
Pulse/frequency/switch output
(passive)
1) 2)
Maximum terminal voltage
DC 35 V
3
A0018161
4 (-)
11